Supply chain dew point temperature evaluation (SplyTDwpEvl11)

Overview

The application function "Supply chain dewpoint temperature evaluation 11" (SplyTDwpEvl11) can be used to dehumidify at the primary air handling unit to avoid condensation.

Function

The application function collects and evaluates the dew point temperature from the room segments in the supply air group. It also counts the number of active condensation monitors in a chilled ceiling application.

The results of the evaluations can be used at the primary air handling unit to dehumidify, but this must be done in a project (dehumidification is project specific).

Configuration

None

Interface

Interface

Description

Type

Ref.

Owned by

AirTDwp

Supply chain air dewpoint temperature
▶ The average of the two highest dewpoints.

MPrcVal

-

AirNumCdnMon

Supply chain air number of active condensation monitor
▶ The number of active condensation monitors.

ACalcVal

-

AirCdnMonRate

Supply chain air rate of condensation monitor
▶ The rate in [%] of the active condensation monitors.

ACalcVal

-

SplyAirMst

Manager for supply chain air

GrpMaster

SplyAir11

Engineering and commissioning

The chilled water supply group also has a function that reduces condensation: a shift-up of the chilled water setpoint. Dehumidification at the AHU and shift-up of the chilled water setpoint must be coordinated.