Supply chain dew point temperature evaluation (SplyTDwpEvl11)
Overview
The application function "Supply chain dewpoint temperature evaluation 11" (SplyTDwpEvl11) can be used to dehumidify at the primary air handling unit to avoid condensation.
Function
The application function collects and evaluates the dew point temperature from the room segments in the supply air group. It also counts the number of active condensation monitors in a chilled ceiling application.
The results of the evaluations can be used at the primary air handling unit to dehumidify, but this must be done in a project (dehumidification is project specific).
Configuration
None
Interface
Interface | Description | Type | Ref. | Owned by |
|---|---|---|---|---|
AirTDwp | Supply chain air dewpoint temperature | MPrcVal | ● | - |
AirNumCdnMon | Supply chain air number of active condensation monitor | ACalcVal | ● | - |
AirCdnMonRate | Supply chain air rate of condensation monitor | ACalcVal | ● | - |
SplyAirMst | Manager for supply chain air | GrpMaster | ◉ | SplyAir11 |
Engineering and commissioning
The chilled water supply group also has a function that reduces condensation: a shift-up of the chilled water setpoint. Dehumidification at the AHU and shift-up of the chilled water setpoint must be coordinated.