Supply chain VAV overridden value (SplyVavOvrr11)
Overview
The application function "Supply chain VAV overridden value 11" (SplyVavOvrr11) allows a technician / balancer to override the VAV applications for balancing and commissioning of the ductwork.
Function
The technician overrides VAV damper position and VAV flow setpoints via SplyAir group distribution to the destination object. See Engineering and commissioning.
Configuration
Parameters
Description | Parameter | Default value |
|---|---|---|
Enable supply air VAV mode overridden value 0:No | EnVavSuModOvrr | 0:No |
Supply air VAV mode overridden value 1:Off | VavSuModOvrr | 2:Control mode |
Enable extract air VAV mode overridden value 0:No | EnVavExModOvrr | 0:No |
Extract air VAV mode overridden value 1:Off | VavExModOvrr | 2:Control mode |
Enable supply air VAV overridden value 0:No | EnVavSuOvrr | 0:No |
Supply air VAV overridden value 0...1000 | VavSuOvrr | 50 |
Enable extract air VAV overridden value 0:No | EnVavExOvrr | 0:No |
Extract air VAV overridden value 0...1000 | VavExOvrr | 50 |
Interface
Interface | Description | Type | Ref. | Owned by |
|---|---|---|---|---|
SplyAirMst | Manager for supply chain air | GrpMaster | ◉ | SplyAir11 |
Engineering and commissioning
The function can be enabled for supply and extract separately.
The priority for overriding is Prio 8.
MP1.2 and higher:
Use EnVavSuModOvrr and VavSuModOvrr (DeviceMode Multistate)
1:Off
2:Control mode
3:Maximum air volume flow
4:Minimum air volume flow
MP1.16:
Use EnVavSuOvrr and VavSuOvrr [% of nominal flow]
Example: PL-Link VAV, mapping will go to the AO for the flow setpoint
Range 0..100% of Nominal Flow