Supply chain VAV overridden value (SplyVavOvrr11)

Overview

The application function "Supply chain VAV overridden value 11" (SplyVavOvrr11) allows a technician / balancer to override the VAV applications for balancing and commissioning of the ductwork.

Function

The technician overrides VAV damper position and VAV flow setpoints via SplyAir group distribution to the destination object. See Engineering and commissioning.

Configuration

Parameters

Description

Parameter

Default value

Enable supply air VAV mode overridden value

0:No
1:Yes

EnVavSuModOvrr

0:No

Supply air VAV mode overridden value

1:Off
2:Control mode
3:Maximum air volume flow
4:Minimum air volume flow
5:Smoke control air volume flow setpoint

VavSuModOvrr

2:Control mode

Enable extract air VAV mode overridden value

0:No
1:Yes

EnVavExModOvrr

0:No

Extract air VAV mode overridden value

1:Off
2:Control mode
3:Maximum air volume flow
4:Minimum air volume flow
5:Smoke control air volume flow setpoint

VavExModOvrr

2:Control mode

Enable supply air VAV overridden value

0:No
1:Yes

EnVavSuOvrr

0:No

Supply air VAV overridden value

0...1000

VavSuOvrr

50

Enable extract air VAV overridden value

0:No
1:Yes

EnVavExOvrr

0:No

Extract air VAV overridden value

0...1000

VavExOvrr

50

 

Interface

Interface

Description

Type

Ref.

Owned by

SplyAirMst

Manager for supply chain air

GrpMaster

SplyAir11

Engineering and commissioning

The function can be enabled for supply and extract separately.

The priority for overriding is Prio 8.


MP1.2 and higher:
Use EnVavSuModOvrr and VavSuModOvrr (DeviceMode Multistate)

1:Off
2:Control mode
3:Maximum air volume flow
4:Minimum air volume flow


MP1.16:

Use EnVavSuOvrr and VavSuOvrr [% of nominal flow]

Example: PL-Link VAV, mapping will go to the AO for the flow setpoint
Range 0..100% of Nominal Flow