Supply chain supply air VAV air volume flow saturation evaluation (SplyVavSuSrt11)

Overview

(for future use)

The application function "Supply chain supply air VAV air volume flow saturation evaluation 11" (SplyVavSuSrt11) evaluates the supply VAV saturation signal(s) from the room segments for use in fan speed optimization.

Function

(for future use)

Depending on the number of supply saturation signals (NumVavSuStrtn) the fan speed can be adjusted.

The signal for damper saturation is a binary value object. It is True when the air flow control loop cannot get enough air to reach setpoint.

The value is True when:

Configuration

None

Interface

Interface

Description

Type

Ref.

Owned by

NumVavSuStrtn

Number of supply air VAV air volume flow starved

ACalcVal

-

SplyAirMst

Manager for supply chain air

GrpMaster

SplyAir11

Engineering and commissioning

By implementation of a project specific solution this function could be used. The value of NumVavSuStrtn can be picked up by the primary AHU by BA-addressing and the fan speed could be set with a function.