BI with Switch on/off delay
The following sections show the properties of binary inputs (BI) with the subsystem- specific extension "Switch on/off delay". Binary inputs with the subsystem- specific extension "Switch on/off delay" are not supported in Desigo 5.x.
Channel configuration properties
The listed properties are displayed in the Hardware and network editor > Inspector window > Properties tab when the data point is selected in the Device view tab.
Number of channels |
|---|
"Number of channels" defines how many channels are used by the data point. If more than one channel is used by the I/O data point, all properties are stored in the first channel. |
Signal type |
|---|
"Signal type" defines the DRA signal type. Available signal types depend on I/O module type. The signal type can be edited. |
Save as
|
|---|
"Save as" saves the set parameters of the I/O data point as an xml-file. |
Subsystem-specific extension properties
The listed properties are displayed in the BACnet objects editor > Inspector window > Properties > Configuration tab when the data point is selected in the editor table.
Note: Additional delays are configured in the application.
✳ Indicates a Siemens proprietary property.
Switch-off delay ✳ |
|
|
|---|---|---|
"Switch-off delay" defines the time delay before the sensor changes from occupied to unoccupied. Range: 00:00...05:00 [min:s] | ||
Switch-on delay ✳ |
|
|
|---|---|---|
"Switch-on delay" defines the time delay before the sensor changes from occupied to unoccupied. Range: 00:00...05:00 [min:s] | ||