Access levels

Access level

Name

Description

1

Internal

Access to all BACnet objects and properties for very specialized actions e.g. during development.

2

Extended service

Not used by HQ solutions yet.

3

Basic service

Access to BACnet objects and properties used for commissioning, e.g. configuration value extensions, I/O extensions, etc.

4

Administrator

Not used by HQ solutions yet.

5

Extended operation

Access to BACnet objects and properties for extended operation and monitoring such as network and device objects. All I/Os are visible

6

Standard operation

Access to BACnet objects and properties for standard operation and monitoring (daily business), .e.g. room and plant information on a management station.

7

Basic operation

Access to BACnet objects and properties for a room user e.g. data points visible on a room unit.

For each BACnet object an access level is predefined. You can define corresponding access levels for each user role in Settings > User profiles > Roles.
Roles tab

Depending on the defined access level definitions of the user role, BACnet objects are readable or writable in the web interface.

Example
A control parameter has a predefined access level Internal. If the defined user has the access level Basic service defined, he is not granted access to the control parameter.