Emergency Lighting object (EmgLgt)
✳ Indicates a Siemens proprietary property.
Present value |
|
|
|---|---|---|
'Present value' indicates the present value of the virtual variable. | ||
Property ID: 85 | ||
DALI device number ✳ |
|
| |
|---|---|---|---|
"DALI device number" identifies a possible attached DALI device. The property value represents a possible dependency between an emergency unit and a lighting unit. | |||
0 | No dependency between an emergency unit and a lighting unit | ||
Dali device number | Dependency between a coupled emergency unit and a lighting unit | ||
| |||
Attached-To-Dali-Device = 0: No dependency between an emergency unit and a lighting unit
Attached-To-Dali-Device = Dali device number
-Dependency between a coupled emergency unit and a lighting unit
-Dali device number represents a forward reference from the emergency control gear to the device number of the Control Gear that is coupled with the emergency control gear.
-The emergency control gear will disconnect the coupled lighting control gear if emergency mode or test procedure is active, i.e. the coupled lighting control gear will no more communicate on DALI.
-In the case the data acquisition will suppress Reliability errors of the corresponding Peripheral-Device-Object, will stop the running of control commands received from the respective BA-Lighting-Output-Object and set the Status-Flag Overridden of the Lighting Output Object to indicate that the actuator is locally overridden by an emergency mode or test procedure.
Short test time ✳ |
|
|
|---|---|---|
"Short test time" defines the short duration test period in seconds. | ||
Test period ✳ |
|
|
|---|---|---|
"Test period" defines the start and frequency of test periods in days. Tests can be started automatically or manually. The following tests are available.
Setting the value to 0, will start the tests manually. If the duration test and short duration test are set to start automatically (> 0), the lower value will be used as the primary test type. | ||
Control command ✳ |
|
| |
|---|---|---|---|
"Control command" allows triggering and canceling tests, as well as changing the mode of emergency lights.
| |||
Ready | Default value | ||
Start-Function-Test | Triggers a function test. | ||
Start-Duration-Test | Triggers a duration test. Present-Value indicates whether a duration test is active. | ||
Start-Short-Duration-Tests | Triggers a short duration test. Present-Value indicates whether a duration test is active. | ||
Stop-Test | Cancels an active test. | ||
Goto-Rest-Mode | Sets the emergency light to rest mode. | ||
Goto-Inhibit-Mode | Sets the emergency light to inhibit mode. | ||
Re-Light | Cancels the inhibit mode and the Control Gear will revert to emergency mode unless further inhibited by the hardwired inhibit. | ||
Reset-Inhibit | Cancels the inhibit mode and the Control Gear will revert to normal mode. | ||
Reset-Lamp-Time | Clears the lamp operation time information in case of replacement of the lamp. The control gear counters Lamp EMERGENCY TIME and LAMP TOTAL OPERATION TIME and the properties Lamp-Emergency-Time and Lamp-Total-Operation-Time will be reset. | ||
Control command result ✳ |
|
| |
|---|---|---|---|
"Control command result" indicates the running result of last Control-Command. | |||
0 | Unknown (default) | ||
1 | Function-test-initiated | ||
2 | Duration-test-initiated | ||
3 | Short-duration-test-initiated | ||
4 | Stop-test-performed | ||
5 | Stop-test-discarded (no-test-active) | ||
6 | Goto-rest-mode-performed | ||
7 | Goto-rest-mode-discarded (mode) | ||
8 | Goto-inihibit-mode-performed | ||
9 | Goto-inhibit-mode-discarded (mode) | ||
10 | Re-light-performed | ||
11 | Re-light-not-supported | ||
12 | Re-light-discarded (mode) | ||
13 | Re-light-discarded (hardwired-inhibit) | ||
14 | Reset-inhibit-performed | ||
15 | Reset-inhibit-discarded (mode) | ||
16 | Reset-lamp-time-performed | ||
17 | Reset-lamp-time-failed | ||
18 | Discarded (test-already-in-progress) | ||
Switch-on delay for mains supply ✳ |
|
|
|---|---|---|
"Switch-on delay for mains supply" defines an extension of an emergency period in seconds before returning to normal mode. The property can be modified online. | ||
Emergency lighting level ✳ |
|
|
|---|---|---|
"Emergency lighting level" defines the emergency lighting level in percent. Only use the property during commissioning. Do not modify the property during normal operation. It has a high write access level. If the "Emergency lighting level" value is -1%, the value can only be used with peripheral devices which support a configurable emergency level. | ||
I/O address ✳ |
|
|
|---|---|---|
"I/O address" identifies and documents the data source, and facilitates configuring, modifying, and querying the assignment in a standardized way. The content of "I/O address" is technology-specific and includes:
| ||
State text |
|
|
|---|---|---|
'State text' specifies the enumeration of the multistate value. Preconfigured enumerations can be selected or set to a project-specific enumeration. | ||
Property ID: 110 | ||
Emergency luminaire type ✳ |
|
| |
|---|---|---|---|
"Emergency luminaire type" identifies the emergency converter type. | |||
0 | Unknown | ||
1 | Switched-maintained-dimmable-control-gear | ||
2 | Switched-maintained-non-dimmable-control-gear | ||
3 | Maintained-control-gear | ||
4 | Non-maintained-control-gear | ||
Battery charge ✳ |
|
| |
|---|---|---|---|
"Battery charge" indicates the actual charge level of the battery. | |||
0% | Unknown battery charge level. Actual value cannot be determined by the Data Acquistion. | ||
Battery state ✳ |
|
| |
|---|---|---|---|
"Battery state" indicates the actual state of the battery. | |||
0 | Unknown | ||
1 | Battery-fully-charged | ||
2 | Battery-charge-in-progress | ||
3 | Battery-failure | ||
Expected emergency operating hours ✳ |
|
| |
|---|---|---|---|
"Expected emergency operating hours" identifies the rated battery backup time in seconds. | |||
0 | Unknown value | ||
Emergency lamp operating hours ✳ |
|
| |
|---|---|---|---|
"Emergency lamp operating hours" indicates the accumulated time in seconds during which the lamp has been emergency switched on. | |||
0 | Unknown value | ||
Total lamp operating hours ✳ |
|
| |
|---|---|---|---|
"Total lamp operating hours" indicates the accumulated time in seconds during which the lamp has been switched on.
| |||
0 | Unknown value | ||
Out of service |
|
|
|---|---|---|
"Out of service" allows decoupling the object from being modified by a control program, system program or peripheral device.
| ||
Property ID: 81 | ||
State flag ✳ |
|
|
|---|---|---|
"State flag" represents four boolean flags ("Out of service", "Overridden", "Fault", "In-Alarm") that indicate the general status of an object. | ||
Reliability |
|
|
|---|---|---|
'Reliability' indicates whether the property value 'Present value' is reliable. If the 'Present value' is not reliable, the property 'Reliability' indicates the cause of the fault and the bit "Fault" of the state indication is set to 'True'. In a normal case, the property 'Reliability' is set to "No fault". | ||
Property ID: 103 | ||
Tracking value |
|
|
|---|---|---|
'Tracking value' represents the uncorrected value as measured by the subsystem. It has the same data type as the 'Present value'.
| ||
Property ID: 5107 | ||
Tested emergency lamp operating hours ✳ |
|
| |
|---|---|---|---|
"Tested emergency lamp operating hours" identifies the battery duration test result of the last duration test in seconds. | |||
0 | Unknown value | ||
Test state ✳ |
|
| |
|---|---|---|---|
"Test state" indicates whether a test is pending. Tests survive power failure of devices. | |||
0 | Unknown | ||
1 | Test-not-pending | ||
2 | Test-pending | ||
Last test result ✳ |
|
| |
|---|---|---|---|
"Last test result" indicates the result state of the last test. | |||
0 | Unknown | ||
1 | Passed | ||
2 | Failed | ||
3 | Failed-battery-duration | ||
4 | Test-manually-stopped | ||
Last test state ✳ |
|
| |
|---|---|---|---|
"Last test state" indicates the running state of the last test. | |||
0 | Unknown | ||
1 | In-time | ||
2 | Max-delay-exceeded | ||
Last test mode ✳ |
|
| |
|---|---|---|---|
"Last test mode" indicates the start method of the last test. | |||
0 | Unknown | ||
1 | Automatic | ||
2 | Manual | ||
Last test start ✳ |
|
|
|---|---|---|
"Last test start" indicates the start date and time of the last test. | ||
Last test end ✳ |
|
|
|---|---|---|
"Last test end" indicates the end date and time of the last test. | ||
Object access level ✳ |
|
| ||
|---|---|---|---|---|
"Object access level" defines the instance-specific object access level. "Object access level" is used for generic filtering and processing an object by a client application.
| ||||
Access level | Name | Description | ||
7 | Basic operation | Access to BACnet objects and properties for a room user e.g. data points visible on a room unit. | ||
6 | Standard operation | Access to BACnet objects and properties for standard operation and monitoring (daily business), .e.g. room and plant information on a management station. | ||
5 | Extended operation | Access to BACnet objects and properties for extended operation and monitoring such as network and device objects. All I/Os are visible | ||
4 | Administrator | Not used by HQ solutions yet. | ||
3 | Basic service | Access to BACnet objects and properties used for commissioning, e.g. configuration value extensions, I/O extensions, etc. | ||
2 | Extended service | Not used by HQ solutions yet. | ||
1 | Internal | Access to all BACnet objects and properties for very specialized actions e.g. during development. | ||
Object usage ✳ |
|
|
|---|---|---|
"Object usage" indicates whether the object is used or unused. The "Object usage" property can hide or display respective objects and their functionality in a client. For example, room functionality can be marked for flexible room arrangements as used/unused. An object that is marked as unused behaves as if the object does not exist. | ||
Property ID: 4930 | ||
Description |
|
|
|---|---|---|
"Description" is a string of printable characters whose content is not restricted. | ||
Object name |
|
|
|---|---|---|
"Object name" represents a name for the object that is unique internetwork-wide. The minimum length of the string is one character. The set of characters used in the "Object name" are restricted to printable characters. | ||
Comment |
|
|
|---|---|---|
A string of printable characters whose content is not restricted. | ||