Fume hood sash, double vertical and external (FhSash12)

Overview

The application function "Fume hood sash 12, double vertical and external" (FhSash12) is used to calculate the face area of a fume hood with two side by side vertical sashes.

Main features:

Function

 

Command or request (or related)

Notification of condition or status, or availability

Device mode

Interlock (internal signal, not a BACnet object; see Interlocks section for additional information)

Face area calculation:

Face area is a calculated value that uses the following:

Note
FhExtFaceAreais only used in the FhFaceArea calculation when ExtFaceArea is set to yes.

Face area valid signal: The FaceAreaVld output is used by other modules to determine if the general fume hood failure alarm should be active and to set other objects to valid.

The FaceAreaVld signal is a combination of valid signals from the sash 1 position sensor and external face area. ExtFaceArea is used to determine if there is an active external face area device.

The output will only be ON and FhFaceArea will only be set valid when:

OR

Note
Sash sensor(s) must be calibrated. See Sash calibration and verification in Technical principals for more information.

 

Feature configuration

Feature selections for "Room HVAC coordination" are accessed via the Application configuration task in the Configuration component.

Feature (AF)

Feature description

Ref.

Trend for fume hood face area

None/Active

Configuration

Parameters

Description

Parameter

Default value

External face area

▶ Set to Yes if a Sash Open Area Module is connected on SCOM.

0:No
1:Yes

ExtFaceArea

0:No

Sash track height
▶ Fully open the sash. If there is no fixed panel in the plane of the sash opening that is lower than the bottom of the sash, leave SashTckHgt at the default (0 inches (cm)). If there is a fixed panel in the plane of the sash opening that is lower than the bottom of the sash, measure the distance from the bottom of the sash opening to the bottom of the fixed panel in inches (cm). Set SashTckHgt to this value.

SashTckHgt

0 [cm]
0.0 [in]

Width of vertical sash 1
▶ Measure the width of vertical sash 1 in inches (cm). Set WdtVrtSash1 to this value.

WdtVrtSash1

0 [cm]
0.0 [in]

Width of vertical sash 2
▶ Measure the width of vertical sash 2 in inches (cm). Set WdtVrtSash2 to this value.

WdtVrtSash2

0 [cm]
0.0 [in]

Height of bypass opening
▶ Open the sash until the top edge of the sash is aligned with the top edge of the bypass area, closing the bypass area. Measure the height of the sash opening in inches (cm). Set HgtBypOpn to this value.

HgtBypOpn

0 [cm]
0.0 [in]

Unrestricted bypass opening
▶ If there is no restriction on the bypass, leave BypOpnUrstd at the default (100%). If the bypass area has an airflow restrictor covering the open area, such as a perforated grille or louvers, estimate the open percentage of the bypass area. Set BypOpnUrstd to the appropriate value.

BypOpnUrstd

100 [%]

Total area of fixed openings
▶ Measure the fixed area of the fume hood in square feet (m2). Any fume hood leakage must be accounted for in this measurement. Set TotAreaFixOpn to this value.

TotAreaFixOpn

0 [m2]
0.0 [ft2]

Area on sensor failure
▶ Set AreaSenFail to the value that will be used as the fume hood face area in the event of a sash sensor failure.

AreaSenFail

0.5 [m2]
5.38 [ft2]

Length unit
▶ Defined by selected engineering unit – do not change.

LngtUnit

[cm]
[in]

Area unit
▶ Defined by selected engineering unit – do not change.

AreaUnit

[m2]
[ft2]

Interface

Interface

Description

Type

Ref.

Owned by

FhExtFaceArea

Fume hood external face area

AI

Room segment / Field device

FhSash1Pos

Fume hood sash 1 position

AI

Room segment / Field device

FhSash2Pos

Fume hood sash 2 position

AI

Room segment / Field device

FhFaceArea

Fume hood face area

ACalcVal

-

TrndFhFaceArea

Trend for fume hood face area

FtrSel

-

Engineering and commissioning

Optional.