QMX3.P87, P88 device properties
The listed properties are displayed in the Hardware and network editor > Inspector window > Properties tab when the device with KNX PL-Link is selected in the Device view tab.
QMX3.P87 | QMX3.P88 |
|
|
|
|
|
|
General and Catalog information
The General and Catalog Information group provides information about the device.
Property | Description | Default value |
|---|---|---|
Mode | Mode shows the network mode of the device. Read only. | KNX PL-Link |
Name | Name is a text field to enter the name of the device. The name is used to identify the device in the device view. | Depends on other settings. |
Comment | Comment is a free text field to enter any helpful information on the device. | - |
Power consumption | Power consumption shows the power the device consumes. Read only. Unit: [mA] The value is used to calculate the remaining power of the KNX rail. See also power consumption and supply on KNX rail of PXC3 or KNX rail of DXR2. | Depends on the device type. |
Short designation | Short designation shows a short description of the device. Read only. | Depends on the device type. |
Order number | Order number shows the device type. Read only. | Depends on the device type. |
Version | Version shows an internal version of the device. Read only. | - |
Description | Description shows a short description of the device. Read only. | Depends on the device type. |
Device information
The Device information group provides information about the device and settings.
Property | Description | Default value |
|---|---|---|
Device address (KNX) | Device address (KNX) shows the fixed standard address for devices with KNX PL-Link. Read only. | 255 |
Network address (KNX) | Network address (KNX) shows the network address that was assigned based on the device address (KNX). Read only. | 0.2.255 |
Serial number used | Serial number used defines the method used for device identification.
|
|
Serial number | Serial numberis a text field to enter the serial number used for device identification. Serial number is only enabled and meaningful if Serial number used is enabled. | 000000000000 |
Push buttons - QMX3.P87 | Use the drop-down list to define the operation for each Function key. Function keys 1, 2, 6, and 7:
Function key 3:
Function key 4 Fume hood internal light Function key 5 Green leaf button Function key 8 Sash closer button Function key 9
Function key 10
| Function keys 1, 2, 6, and 7: Function key 3: Function key 9: Function key 10: |
Push button - QMX3.P88 | Function key 9
|
|
Active unit set
| Active unit set defines the unit for the display of the actual face velocity and actual face velocity setpoint or actual airflow and airflow setpoint.
|
|
Alarming
Property | Description | Default value |
|---|---|---|
Alarming |
|
|
Functions
The functions table in the Channel Overview provides an overview of the channels of the device. Depending on the device the values in the table are read only or can be edited. The available types depend on the device and the application function.
Property | Description |
|---|---|
Name | Name of the channel. Read only. |
Type | Name of the function. |
Zone | Part of the geographical address of the device. Range: 1...126 |
Room | Part of the geographical address of the device. Range: 1...63 |
Subzone | Part of the geographical address of the device. Range: 1...15 Note |
Energy efficiency function (EEF)
Property | Description | Default value |
|---|---|---|
Activate | Enables or disables the "Green Leaf" function.
|
|
Change to green | Defines the conditions for the "Green Leaf" LED to turn green.
|
|
User ODP display (UODPD)
Property | Description | Default value |
|---|---|---|
Buzzer mode status timeout | Specifies the timeout value in seconds. Range: |
|
Buzzer mode status heartbeat | Defines the time interval to report the process value if the value did not change or the change was smaller than the Change of value, COV. Range: | 120 |
Buzzer mode status heartbeat | Range: |
|
Buzzer mode timeout | Range: |
|
User fume hood mode setting (UFHMS)
Property | Description | Default value |
|---|---|---|
PrioTresh fume hood mode user locked | Range: | 13 |


: The serial number entered in the text field Serial number is used for device identification.
: Device identification has to be done in Web interface. The device has to be in programming mode for Web interface to perform the device identification.
No function
0…65535 [s]