QMX3.P35H, P38H device properties
The listed properties are displayed in the Hardware and network editor > Inspector window > Properties tab when the device with KNX PL-Link is selected in the Device view tab.
QMX3.P35H | QMX3.P38H |
|
|
|
|
|
|
General and Catalog information
The General and Catalog Information group provides information about the device.
Property | Description | Default value |
|---|---|---|
Mode | Mode shows the network mode of the device. Read only. | KNX PL-Link |
Name | Name is a text field to enter the name of the device. The name is used to identify the device in the device view. | Depends on other settings. |
Comment | Comment is a free text field to enter any helpful information on the device. | - |
Power consumption | Power consumption shows the power the device consumes. Read only. Unit: [mA] The value is used to calculate the remaining power of the KNX rail. See also power consumption and supply on KNX rail of PXC3 or KNX rail of DXR2. | Depends on the device type. |
Short designation | Short designation shows a short description of the device. Read only. | Depends on the device type. |
Order number | Order number shows the device type. Read only. | Depends on the device type. |
Version | Version shows an internal version of the device. Read only. | - |
Description | Description shows a short description of the device. Read only. | Depends on the device type. |
Device information
The Device information group provides information about the device and settings.
Property | Description | Default value |
|---|---|---|
Device address (KNX) | Device address (KNX) shows the fixed standard address for devices with KNX PL-Link. Read only. | 255 |
Serial number used | Serial number used defines the method used for device identification.
|
|
Serial number | Serial numberis a text field to enter the serial number used for device identification. Serial number is only enabled and meaningful if Serial number used is enabled. | 000000000000 |
Rows functions (QMX3.P38H only) | Rows functions defines which function is applied to which channel row.
HVAC: Heating, ventilating, and air conditioning. Read only. LDSB: Light dimming sensor basic. Read only. SSSB: Sunblind sensor basic. Read only. | For all rows: LDSB |
The functions are described briefly in the table below. The assortment of functions depends on the device.
Alarming
Property | Description | Default value |
|---|---|---|
Alarming |
|
|
Functions
The functions table in the Channel Overview provides an overview of the channels of the device. Depending on the device the values in the table are read only or can be edited. The available types depend on the device and the application function.
Property | Description |
|---|---|
Name | Name of the channel. Read only. |
Type | Name of the function. |
Zone | Part of the geographical address of the device. Range: 1...126 |
Room | Part of the geographical address of the device. Range: 1...63 |
Subzone | Part of the geographical address of the device. Range: 1...15 Note |
Activate | Activate defines if the channel is activated.
|
Some of the functions can be configured. The properties of those functions are described below in alphabetical order.
Room temperature sensor (RTS)
Property | Description | Default value |
|---|---|---|
Change of value, COV | Change of value, COV defines the change in the process value that triggers the sending of the process value. Range: | 0.1 |
Heartbeat | Heartbeat defines the time interval to report the process value if the value did not change or the change was smaller than the Change of value, COV. Range: | 120 |
Minimum repetition time | Minimum repetition time defines the minimal time interval before the next process value can be sent. Range: | 10 |
Scene sensor (SCS)
Property | Description | Default value |
|---|---|---|
Memorize | Memorize defines if scenes can be saved using teach-in.
|
|
Scene function | Defines if the numbered scene will be recalled or saved.
|
|
TeachInDisable | TeachInDisable defines if the current settings for a given scene can be saved. Read only.
|
|
Active | Active defines if a predefined scene is available on the room operator unit.
|
|
Number | Number defines to which predefined scene the settings in the row apply. Range: 1...12 1: Presentation 2: Meeting 3: Break 4: Occupied 5: Vacant 6: Do not disturb 7: Cleaning 8: Service 9: Sleep 10: Entertainment 11: Brighter 12: Darker | Depends on other settings. |
Pulse length | Pulse length defines how long a pushbutton has to be pressed to be detected as a long key press. Property is used to differentiate between a recall (short key press) or a teach-in (long key press) command. Range: | 50 |
User HVAC display
The outside sensor zone is supported by both QMX3.P35H and QMX3.P38H
Property | Description | Default value |
|---|---|---|
Outside sensor zone | Outside sensor zone defines which outside sensors provide data to the room operator unit. Outside sensors are assigned to outside sensor zones instead of geographical addresses (building zone, room, subzone). Range: | Depends on other settings. |
Enable temp room |
| Enabled |
User HVAC room settings (UHRS)
Property | Description | Default value |
|---|---|---|
Manual mode | Sets the priority for the property. Range: | 13 |
Operation limit for operation mode | Sets the priority for the property. Range: | 13 |
Operation limit for setpoint | Sets the priority for the property. Range: | 13 |
Operation limit for presence button | Sets the priority for the property. Range: | 13 |
Setpoint resolution | Setpoint resolution defines the smallest adjustment of the room temperature setpoint that users can make. Range: | 1 |
User fan speed setting (UFS)
Property | Description | Default value |
|---|---|---|
Enable rapid ventilation1) | Enable rapid ventilation defines if the user can start rapid ventilation.
|
|
Number of stages1) | Number of stages defines the type of speed control of the connected fan. Range: 1...3: staged speed control fan (1, 2, 3 stages) 4...99: not supported 100: variable speed control | 3 |
Manual mode | Sets the priority for the property. Range: | 13 |
Operation limit for fan speed | Sets the priority for the property. Range: | 13 |
Energy efficiency function (EEF)
Property | Description | Default value |
|---|---|---|
Activate | Enables or disables the "Green Leaf" function.
|
|
Change to green | Defines the conditions for the "Green Leaf" LED to turn green.
|
|
Extended device
Property | Description | Default value |
|---|---|---|
Active unit set |
| Metric (Centigrade) |
Room unit device object (RUDO)
Property | Description | Default value |
|---|---|---|
EnableContrModeAct | EnableContrModeAct state enables or disables the display of the plant state.
|
|
Enable fan speed | Enable fan speed defines if the fan speed is displayed and if the user can change the fan speed.
|
|
Enable HVAC mode | Enable HVAC mode defines if the present operating mode is displayed.
QMX3 interface: RClmOpModIn, RClmOpModRu |
|
Enableroomoccupancy | Enableroomoccupancy defines if the user can influence the room operating mode by confirming his presence.
|
|
EnableHumRelSetp | EnableHumRelSetp defines if any relative humidity values are displayed.
|
|
Enable Cmf prolong | Enable Cmf prolong defines if the comfort prolongation function for room occupancy is enabled.
|
|
Enable TP setup shift | Enable TP setup shift defines if the temperature setpoint or the shift of the temperature setpoint is displayed and if the user can change either.
|
|
Temp setp user op type | Type defines how the shift in the temperature setpoint is displayed.
|
|
UlIdletime | UIIdletime defines the time before the display returns from the presently active page to the default page (see Default display). Range: | 60 |
BackLightIdletime | BackLightIdletime defines the time before the backlight is turned of after the last operation of a key. Range: | 15 |
Uldefaultpage | Uldefaultpage defines which page is displayed after the 'Return to default display' time has passed.
|
|
Enablefinedustdisplay | Enablefinedustdisplay defines which particulate matter values can be displayed.
|
|
Enable temp display | Enable temp display defines which temperature values can be displayed.
|
|
Enable hum rel display | Enable hum rel display defines which relative humidity values can be displayed.
|
|
Enable AQ display | Enable AQ display defines which air qualities can be displayed.
|
|
User presence switch (UPS)
Property | Description | Default value |
|---|---|---|
Operation limit for presence status | Sets the priority for the property. Range: | 13 |
User relative humidity setpoint settings (URHSS)
Property | Description | Default value |
|---|---|---|
Step increment HMI | Increment defines the value by which the relative humidity setpoint changes, each time the key is pressed. Range: | 1 |
PrioThreshHumRelSetp user locked | Sets the priority threshold for the relative humidity setpoint below which the user interference is blocked. Range: | 13 |
Light dimming sensor basic (LDSB)
Property | Description | Default value |
|---|---|---|
Pulse Length | Pulse length defines the configuration data property that provides the time to detect a long press on a push button to differetiate between a short key press and a long key press. | 5 |


: The serial number entered in the text field Serial number is used for device identification.
: Device identification has to be done in Web interface. The device has to be in programming mode for Web interface to perform the device identification.
List of available functions:
0.1...1.0 [K]


and influence the operating mode.