Analog scheduler (ASchedule)

The object type scheduler analog includes the BACnet properties for an analog scheduler.

Naming

There is a dependency between 'Name', 'Description' and 'Naming extension'. Any changes to one impacts the other two properties.

Note:
The dependency can be eliminated by entering a project-specific text.

Example 1:
The preconfigured 'Description' "Room operating mode scheduler" sets the 'Name' to "ROpModSched" if selected. If "A" is selected as a supplement to the 'Naming extension', the description is supplemented by "(ventilation and air conditioning)" to "Room operating mode scheduler (ventilation and air conditioning)" and the 'Name' becomes "ROpModSched(A)". The name also forms the last element of the object name.

Example 2:
The preconfigured 'Description' "Domestic hot water scheduler" sets the 'Name' to "DhwSched" if selected. Selecting "01" (project-specific text) in addition to 'Naming extension', results in the 'Name' "DhwSched(01)". The name also forms the last element of the object name.

Name

 

 

'Name' is a name specific to the instance. It is used to set up a hierarchical object name.

Property ID: 4438

Description

 

 

'Description' describes a BACnet object. The 'Description' is a translatable string that is saved internally as a text reference or directly as a string.

Property ID: 28

Name extension

 

 

'Name extension' is an optional extension of the name. It uniquely identifies an object or to distinguish objects.

Property ID: 4437

Note
Designations from the text catalog can also be used for the 'Naming extension'.

Object name

 

 

'Object name' uniquely designates a BACnet object within an automation station.

Property ID: 77

Object naming rule

 

 

'Object naming rule' defines the rule for setting object names during engineering. The value range is either 'hierarchical' or 'customized'. Under 'hierarchical', the object name is formed based on the hierarchy. The object name is set directly under 'Customized'. The BACnet hierarchy structure is irrelevant.
Note
'Object naming rule' is an internal property. It is not accessible via the standard right/write procedure.

Property ID: 4436

Other

Schedule default value

 

 

'Schedule default value' set the default value used for 'Present value' if no other if not other scheduler value is active.
The scheduler default value is between 'Present minimum value' and 'Present maximum value'.

Property ID: 174

Priority for writing

 

 

'Priority for writing' sets the priority to command objects entered in the object list.
Priority range: 1...16

Property ID: 88

Note
The object list can only be modified online with a BACnet browser in the current tool version.

Suppress fault monitoring

 

 

'Suppress fault monitoring' determines whether the fault supervision (fault events) is suppressed ('Yes'/'No'). The setting 'Yes' suppresses the evaluation of 'Reliability' and the value for 'Reliability' remains on "No fault".

Property ID: 357

Out of service

 

 

"Out of service" allows decoupling the object from being modified by a control program, system program or peripheral device.

  • If "Out of service" is TRUE, the properties "Present value" and "Reliability" will no longer be updated by the respective control program, system program or peripheral device.
  • If "Out of service" is TRUE, the properties "Present value" and "Reliability" can be modified for simulating and testing purposes.
  • If "Out of service" will be changed from FALSE to TRUE, the properties "Present value" and "Reliability" keep their values. Nevertheless, they can be individually modified afterwards.
  • If "Out of service" will be changed from TRUE to FALSE, the properties "Present value" and "Reliability" keep their values. They will be modified by the next update of the producer.

Property ID: 81

Units

 

 

'Units' displays the physical unit of 'Present value'.

Property ID: 117

Resolution

 

 

'Resolution' indicates the accuracy that a value represents. It defines the smallest recognizable change in engineering units of the property 'Present value' and be modified online.
'Resolution' is typically used for operating and monitoring functions to represent the 'Present value':
'Resolution' can only be an integer > 1.
'Resolution' is only used for an abbreviated depiction on the display, e.g. a station for operating and monitoring. It is not used to shorten the actual value that is processed by the program.

Property ID: 106

'Present maximum value'

 

 

'Present maximum value' sets the highest value for the present value. Values greater than the configured maximum value are limited to the maximum value.

Property ID: 65

Present minimum value

 

 

'Present minimum value' sets the lowest value for the present value. Values less than the configured minimum value are limited to the minimum value.

Property ID: 69

Object access level

 

 

'Object access level' defines the instance-specific object access level. 'Object access level' is used for generic filtering and processing of an object by a client application.

  • 'Object access level' is a configuration property that can only be set up offline (ABT, application configuration).
  • 'Object access level' is evaluated by the client applications.

Access level

Name

7

Basic operation

6

Standard operation

5

Extended operation

4

Administrator

3

Basic service

2

Extended service

1

Internal

Property ID: 4941

Object usage

 

 

"Object usage" indicates whether the object is used or unused. The "Object usage" property can hide or display respective objects and their functionality in a client. For example, room functionality can be marked for flexible room arrangements as used/unused. An object that is marked as unused behaves as if the object does not exist.

Property ID: 4930

Object identifier

 

 

'Object identifier' is an invariant designator that uniquely identifies the object within an automation station.

Property ID: 75

Naming parent

 

 

'Naming parent' refers to the superposed BACnet object as per the (application) hierarchy.

  • The superposed object can refer to one BACnet object on the same device. A reference to a remote device is not possible.
  • The superposed BACnet object can refer to a BACnet object that is part of the common system hierarchy.

Property ID: 4398