[PRDVHCTL] Predictive heating controller

Function block PRDVHCTL calculates the flow temperature setpoint for heating applications.

PRDVHCTL calculates the flow temperature setpoint for heating applications. A forward-looking, model-based and adaptive controller uses a building and heat transfer model. Moreover, the future room temperature setpoint also considers schedulers and an outside air temperature forecast. Outside air temperature forecast can be based on past outside air temperature measurements performed by PRDVHCTL or supplied to PRDVHCTL via external sources.

Functioning
  • PRDVHCTL can be enabled or disabled via input [EnFnct].
  • A constant value via input [OoServ] can replace the flow temperature setpoint.
  • Adapting building model parameters can be enabled or disabled via input [EnAda].
  • The use of adapted building model parameters can be enabled or disabled via input [TkvAda].
  • The adapted building model parameters can be reset via input [ResetAda].

Calculations

PRDVHCTL calculates the optimum flow temperature setpoint [SpTFl], the optimized present operating mode [PrOpMod] and enabled heat distribution [EnHDstr] with the help of the following input values:

  • Present room temperature [TR] (optional).
  • Present flow temperature [TFl].
  • Present outside air temperature [TOa].
  • For [EnExtTOa] = 1, the outside air temperature forecast values [ExtTOa0]...[ExtTOa24] are used.
  • Present operating mode for room [OpModR] with the associated room temperature setpoint [SpHCmf]/[SpHPcf]/[SpHEco]/[SpHPrt].
  • The next operating mode for room [NxOpModR] with the associated room temperature setpoint [SpHCmf]/[SpHPcf]/[SpHEco]/[SpHPrt] and time to next operating mode [TnxOpMod].
  • Building model parameters [SpTFlDs], [SpTFlHi], [ExpRad], [TcnBldg], [TcnRoom], [DTRCoef], [WndProp] or their adapted values.

Optimization is calculated every 15 minutes. [TiNxOpt] displays the remaining time to the next calculation. [OptSta] displays the status of optimization.

The calculation includes the following steps:

Process step

[OptSta]

1

PRDVHCTL adapts the building model parameters.

Preparation

[EnAda] = 1

[OpSta] = 1

[TRSen] = 1

[ErTR] = 0

[ErTFl] = 0

[ErTOa] = 0

PRDVHCTL adapts the building model parameters based on the present measured values [TR], [TFl] and [TOa].

All other cases

Building model parameters are not adapted.

2

PRDVHCTL updates the state estimate of the building model.

The estimated room temperature [TREst] is issued.

Applied building model parameters:

 

[AdaSta] = 1

PRDVHCTL adapts the building model parameters.

 

[AdaSta] = 0

PRDVHCTL uses the configured building model parameters.

 

Applied room temperature values:

 

[TRSen] = 1

The calculation of state estimate is run using the measured room temperature [TR].

 

[TRSen] = 0

The measured room temperature [TR] is used for the initial calculations of the state estimate (initialization).

3

PRDVHCTL calculates the response of the predictive room temperature setpoint [SpTRPd0]...[SpTRPd21] based on scheduler information.

 

[EnNxOpMod] = 1

The future room temperature setpoint response is calculated with the help of [NxOpModR] and [TnxOpMod] from the scheduler.

 

[EnNxOpMod] = 0

The future room temperature setpoint response is the same as the present room temperature setpoint [SpTR] (e.g. for a manual intervention).

4

The function block predicts future outside air temperature [TOaPd0]…[TOaPd20] based on past outside air temperature or external values.

 

[EnExtTOa] = 1

The block predicts future outside air temperature based on external forecast values [ExtTOa0]… [ExtTOa24].

 

[EnExtTOa] = 0

The block predicts future outside air temperature based on past outside air temperature.

5

PRDVHCTL calculates the optimum, future curve of the flow temperature setpoint [TFlPd0]...[TFlPd20] and the associated future curves for room temperature [TRPrdv0]...[TRPrdv20] using temperature curves [SpTRPd0]...[SpTRPd20], [TOaPd0]...[TOaPd20], state estimates, and building parameters.

Future curves encompass the next 64 hours. It considers possible shifts over the weekend.

The flow temperature is limited at a minimum by the estimated room temperature [TREst] and at a maximum by the maximum flow temperature. The maximum flow temperature setpoint is equal to [SpTFlMax] if the estimated room temperature matches the nominal room temperature of 20 °C. In general, the maximum flow temperature setpoint is the result of [SpTFlMax] + ([TREst] - 20 °C).

PRDVHCTL provides [TFlPd0], as the first element of the future flow temperature setpoint curve, on the output for the flow temperature setpoint [SpTFl].

Optimization

6

PRDVHCTL calculates enable heat distribution [EnHDstr] based on temperature curves [SpTRPd0]...[SpTRPd20], [TOaPd0]...[TOaPd20], state estimate and building model parameters.

Enable heat distribution [EnHDstr] is set to 1 if the future room temperature curves deviate significantly from the corresponding room temperature setpoint curve.

Check enable heating

[OptSta] provides additional information

Process step

[OptSta]

 

Output [OptSta] also displays the results of optimization after the optimization calculation.

 

 

Optimization successful

Building model parameters are provided to the following outputs: [SpTFlDsO], [SpTFlHiO], [TcnBldgO], [TcnRoomO], [DTRCoefO].

Calculation OK

 

Optimization does not result in a solution.

The calculation may conclude that the (future) room temperature setpoint cannot always be achieved. The maximum flow temperature setpoint is planned [SpTFl] = [SpTFlMax] in this case. Outputs [TFlPd0]...[TFlPd20] and [TRPrdv0]...[TRPrdv20] are not relevant.

Out of Range
Erroneous calculation

 

 

The function is disabled ([EnFnct] = 0).

Finished

 

 

The function is out of service ([OoServ] = 1).

info

Time frames that apply to forecasts [TRPrdv0]...[ TRPrdv20], [SpTRPd0]...[SpTRPd20], [TOaPd0]... [TOaPd20] and [TFlPd0]...[ TFlPd20] are indicated in seconds after start of optimization in [TiPrdv0]...[TiPrdv20].

Enable and disable function

[EnFnct] = 1

Normal operation

[EnFnct] = 0

The function is disabled.

[SpTFl] = Room temperature setpoint [SpHCmf]/[SpHPcf]/[SpHEco]/[SpHPrt] associated to [OpModR].

[EnHDstr] = 1

[PrOpMod] = Disabled

[TRPrdv0]...[ TRPrdv20], [SpTRPd0]...[SpTRPd20], [TOaPd0]...[TOaPd20], [TFlPd0]...[ TFlPd20] and [TiPrdv0]...[TiPrdv20] are set to 0.

Set default value

[OoServ] = 1

The flow temperature setpoint [SpTFl] is replaced by the default value [DefVal].

[SpTFl] = [DefVal]

[EnHDstr] = 1

[PrOpMod] = Command

[TRPrdv0]...[ TRPrdv20], [SpTRPd0]...[SpTRPd20], [TOaPd0]...[TOaPd20], [TFlPd0]...[ TFlPd20] and [TiPrdv0]...[TiPrdv20] are set to 0.

[OoServ] = 0

Normal operation

Use adapted parameters

[TkvAda] = 1

Optimization is calculated using adapted and valid building parameters.

[TkvAda] = 0

The optimization is calculated using configured building parameters.

Example: No adaptation wanted or no room temperature sensor available ([TRSen] = No)

Enable and disable parameter adaptation

[EnAda] = 1

Building model parameters are adapted continuously.

[EnAda] = 0

Building model parameters are not adapted.

Reset adapted building model parameter

[ResetAda] = 1

The adapted building model parameters are reset.

For [EnAda] = 1, all subsequent building model parameters are adapted and used, after a successful acceptance test, to calculate optimization.

[ResetAda] = 0

Normal operation

Select site for room temperature measurements

Room temperature measurements ideally take place in rooms with the highest heat demand, e.g. north-facing rooms and little to no heat gains.

Thermostatic valves are possible and make sense, if PRDVHCTL is used on heating applications with radiators. It is important to not use thermostatic valves in the reference room (i.e. the room where the room temperature is measured). Disable (fully open) where installed. The remaining rooms for the heating circuit can have thermostatic valves.

Building model parameter

PRDVHCTL uses building models to calculate optimization. The model parameters [SpTFlDs], [SpTFlHi], [TcnBldg], [TcnRoom], [DTRCoef], and [WndProp] are configured as constants. They can be adapted by setting [EnAda] = 1. The configured values are only relevant in this case during the initialization phase.

Parameters for nominal heating curve

The parameters for the nominal heating curve [TOaDsgn], [SpTFlDs], [TOaHi], [SpTFlHi], and [ExpRad] describe the relationship between outside air temperature and the flow temperature setpoint for the nominal room temperature setpoint at 20 °C.

  • [TOaDsgn], [SpTFlDs]: Design point for the nominal heating curve (defined per the planning data for the heating plant).
  • [TOaHi], [SpTFlHi]: High temperature point for the nominal heating curve (defined per the planning data for the heating plant).
  • [ExpRad]: Radiator exponent (dependent on the heat output system)

Building type

TcnBldg

TcnRoom

DTRCoef

WndProp

[h]

[DDDD:HH:MM:SS]

[h]

[K]

[%]

Light build

20

0000:20:00:00

0.25 – 0.5

4.5

50

Medium build

50

0002:02:00:00

3.5

50

Heavy build

100

0004:04:00:00

2.5

50

Mast constructions, glass

50

0002:02:00:00

3.0

90

Time constant of building

The time constant of building [TcnBldg] represents the delay by which the room temperature reacts in an unheated building to a change in outside air temperature. The time constant of building is based on the thermal mass of the building and the building's insulation.

The same setpoints can be used for the typical design as used for HRA.

Room temperature difference for intermittent heating

The following heating modes can be used for determining [DTRCoef]:

  • The heating output system with design heating performance (as defined by the nominal room temperature setpoint of 20 °C and the flow temperature setpoint for design outside air temperature [SpTFlDs]) is switched on for 16 hours.
  • The heating output system is completely shut down for 8 hours.

[DTRCoef] is the room temperature difference that is set for this operation (at a constant outside air temperature and constant heat gain).

[DTRCoef] can no longer be preset as desired when setting heating curve parameters and time constants. PRDVHCTL limits the user input of [DTRCoef] to a preset range.

Proportion of windows

The window proportion [WndProp] indicates the heat loss of the windows as a percentage of the entire building shell. The window proportion is not the percentage of window surface area to the overall surface of the building shell. Heat loss from natural ventilation can also be added to heat loss from windows.

The same setpoints can be used for the typical design as used for HRA.

Automatic adaptation from building model parameters

PRDVHCTL uses building model parameters to improve control accuracy. The building model parameters [SpTFiDs], [SpTFiHi], [ExpRad], [TcnBldg], [TcnRoom], [DTRCoef], [WndProp] are parameterized as constants during engineering.

The adaptation function automatically adapts the building model parameters to actual conditions. The calculated, adapted conditions are provided to outputs [SpTFlDsO], [SpTFlHiO], [TcnBldgO], [TcnRoomO], [DTRCoefO]. The adapted building model parameters are stored persistently.

info

To persistently store the parameters, the extension "Predictive heating control" must be enabled as an extension by persistency on the associated BACnet object.

The extension by persistency has the following values:

Adaptation time

The adaptation time is the time period during which the adaptation is performed.

Estimated parameters

Estimated parameters are the currently adapted building parameters.

Estimated array

The estimated array identifies the current adaptation process.

Pins

Input

Description

Data type

Default value
Value range

EnFnct

Enable function

Enables the function.

Boolean

1

0 - The function is disabled.
1 - The function is enabled.

OoServ

Out of service

Boolean

0

0 - Normal function.
1 - [SpTFl] assumes the value of [DefVal].

DefVal

Default value

Default value for [SpTFl], if [OoServ] = 1.

Real

20.0 [°C]
68.0 [°F]

OpModR

Operating mode for room

Present operating mode for room

Integer

4: Pre-Comfort

1…9

1: Inactive
2: Protection
3: Economy
4: Pre-Comfort
5: Comfort
6: NightCool.
7: Purge
8: Stop
9: Start

EnNxOpMod

Enable next operating mode

Boolean

1

0 - The predictive room temperature setpoint [SpTRPd0]...[SpTRPd20] corresponds to the present room temperature setpoint.
1 - The next room operating mode [NxOpModR] and the time to next operating mode [TnxOpMod] are processed to define the predictive room temperature setpoint [SpTRPd0]...[SpTRPd20].

NxOpModR

Next operating mode for room

Next operating mode for room, requested by the scheduler

Integer

2: Protection

1…9

1: Inactive
2: Protection
3: Economy
4: Pre-Comfort
5: Comfort
6: NightCool.
7: Purge
8: Stop
9: Start

TnxOpMod

Time to next operating mode

Time (duration) to next operating mode, requested by the scheduler.

Time

0

OpSta

Operating state

Operating state of the circulating pump in the heating circuit.

Boolean

0

TRSen

Room temperature sensor

Boolean

1

0 - Calculates function block without room temperature measurement ([TR] is only used for initialization).
1 - Calculates function block with the measured room temperature [TR].

TR

Room temperature

Measures the (reference) room temperature.

Real

20.0 [°C]
68.0 [°F]

0.0…50.0 [°C]
32.0…122.0 [°F]

ErTR

Error room temperature

Indicates if the room temperature [TR] is faulty.

Boolean

0

TFl

Flow temperature

Measured flow temperature

Real

20.0 [°C]
68.0 [°F]

0.0...130.0 [°C]
32.0...266.0 [°F]

ErTFl

Error flow temperature

Indicates if [TFI] is faulty.

Boolean

0

TOa

Outside temperature

Real

20.0 [°C]
68.0 [°F]

-100.0…50.0 [°C]
-148.0…122.0 [°F]

ErTOa

Error for outside temperature

Indicates if the outside air temperature [TOa] is faulty.

Boolean

0

EnExtTOa

Enable external outside temperature prediction

Switch on the use of external outside air temperature forecast.

Boolean

0

ExtTOa0...ExtTOa24

External prediction outside air temperature 0... External prediction outside air temperature 24

External outside air temperature forecast by the hour.

Note
[ExtTOa0] has the temperature for the present time.
[ExtTOa1] has the temperature for 1 hour in the future.
The other inputs follow the same logic.

Real

20.0 [°C]
68.0 [°F]

-100.0...50.0 [°C]
-148.0...122.0 [°F]

SpHCmf

Heating setpoint for comfort

Room temperature setpoint for operating mode "Comfort".

Real

21.0 [°C]
69.8 [°F]

5.0...35.0 [°C]
41.0...95.0 [°F]

SpHPcf

Heating setpoint for pre-comfort

Room temperature setpoint for operating mode "Pre-Comfort".

Real

19.0 [°C]
66.2 [°F]

5.0...35.0 [°C]
41.0...95.0 [°F]

SpHEco

Heating setpoint for economy

Room temperature setpoint for operating mode "Economy".

Real

15.0 [°C]
59.0 [°F]

5.0...35.0 [°C]
41.0...95.0 [°F]

SpHPrt

Heating setpoint for protection

Room temperature setpoint for operating mode "Protection".

Real

12.0 [°C]
53.6 [°F]

5.0...35.0 [°C]
41.0...95.0 [°F]

SpTFlMax

Maximum flow temperature setpoint

Real

95.0 [°C]
203.0 [°F]

25.0…130.0 [°C]
77.0…266.0 [°F]

TiStpMax

Maximum stop time

Maximum time (duration) for stop phase

Time

1h

0…3h

TOaDsgn

Design outside temperature

Defined as per heating plant planning data

Real

-11.0 [°C]
12.2 [°F]

-50.0…10.0 [°C]
-58.0…50.0 [°F]

SpTFlDs

Flow temperature setpoint for design outside temperature

Defined as per heating plant planning data

Real

60.0 [°C]
140 [°F]

25.0…130.0 [°C]
77.0…266.0 [°F]

TOaHi

Outside temperature high

Defined as per heating plant planning data

Real

15.0 [°C]
59.0 [°F]

5.0…25.0 [°C]
41.0…77.0 [°F]

SpTFlHi

Flow temperature setpoint for high outside temperature

Defined as per heating plant planning data

Real

30.0 [°C]
86.0 [°F]

20.0…65.0 [°C]
68.0…149.0 [°F]

ExpRad

Radiator exponent

Defines the deviation of the heating curve from a straight line

Recommended setting for typical heating plants:
Radiators – 1.3
Plate heaters – 1.2...1.3
Convectors – 1.25...1.45
Floor heating – 1.1

Real

1.3

1.0…1.5

TcnBldg

Time constant of building

Time

2d_2h

0…200h

TcnRoom

Time constant of room

Time constant for the influence of a jump in flow temperature to the room temperature

Time

15m

0…5h

DTRCoef

Room temperature difference coefficient

Real

5 [deltaK]
9 [deltaF]

0.0...20.0 [deltaK]
0.0...36.0 [deltaF]

WndProp

Proportion of windows

Reference value for percentage of heat loss from windows.

Real

50.0

0.0…100.0 [%]

EnAda

Enable adaptation

Boolean

1

0 - Building model parameters are not adapted.
1 - Building model parameters are adapted.

TkvAda

Takeover adapted parameters

Boolean

1

0 - The adapted building model parameters are not used.
1 - The adapted building model parameters are used to calculate optimization if valid ([AdaSta = 1]).

ResetAda

Reset adaptation

Resets the adapted building model parameters.

Boolean

0

BaObjRef

BA-Object reference
Link between function block and BACnet object.

Structure

---

BaObjRef
> DeviceID

Device identifier
[DeviceID] includes object type and object instance in one ID.
Identifies the device object: local or remote. A local device object can also be identified by value 16#3FFFFF.

Double Word

16#3FFFFF

BaObjRef
> ObjectID

Object identifier
[ObjectID] includes object type and object instance in one ID.
Identifies the object on a device.

Double Word

16#3FFFFF

BaObjRef
> ItemID

Item identifier
[ItemID] represents an index in a view node object that references the BACnet object.
[ObjectID] and [ItemID] together define an indirect reference to the BACnet object.
Value -1 indicates a direct interface.

Integer

-1

 

Output

Description

Data type

Default value
Value range

PrOpMod

Present operating mode

Integer

1: Inactive

1...6

1: Inactive
2: Off
3: On
4: Boost heating
5: Stop
6: Command

SpTFl

Flow temperature setpoint

Real

20.0 [°C]
68.0 [°F]

SpTR

Room temperature setpoint

Real

20.0 [°C]
68.0 [°F]

TREst

Estimated room temperature

Real

20.0 [°C]
68.0 [°F]

EnHDstr

Enable heat distribution

Boolean

0

0 - Disable heat distribution.
1 - Enable heat distribution.

AdaSta

Adaptation state

Boolean

0

0 - Adaptation of building model parameters is switched off or invalid.
1 - Adaptation of building model parameters is switched on and valid.

OptSta

Optimization state

Integer

1: Optimized

1…8

1: Optimized
2: Optimization preparation
3: Optimization
4: Calculation time elapsed
5: Calculation ok
6: Calculation fault
7: Calculation out of range
8: Heat release check

TiNxOpt

Time to next optimization

Time

0

SpTFlDsO

Flow temperature setpoint for design outside temperature output

Output flow temperature setpoint for the design outside air temperature

Real

60.0 [°C]
140.0 [°F]

SpTFlHiO

Flow temperature setpoint for high outside temperature output

Output flow temperature setpoint for high outside air temperature.

Real

30.0 [°C]
86.0 [°F]

TcnBldgO

Time constant of building output

Output for time constant of the building

Time

2d_2h

TcnRoomO

Time constant of room output

Output for time constant of the room

Time

15m

DTRCoefO

Room temperature difference coefficient output

Output for the room temperature different coefficient.

Real

3 [deltaK]
5.4 [deltaF]

TiPrdv

Predictive time points

Time span in seconds after the last start of optimization, for which forecasts [TFlPrdv], [TOaPrdv], [TRPrdv] and [SpTRPrdv] apply.

Structure

-

TiPrdv
> Ele0…Ele20

Element0...20

Forecast of time values

Real

0

TFlPrdv

Predictive flow temperature setpoint

Forecast of flow temperature setpoint

Structure

-

TFlPrdv
> Ele0…Ele20

Element0...20

Forecast of flow temperature setpoints

Real

0 [°C]
32 [°F]

TOaPrdv

Predictive outside temperature

Forecast outside air temperature

Structure

-

TOaPrdv
> Ele0…Ele20

Element0...20

Forecast of outside air temperature values

Real

0 [°C]
32 [°F]

TRPrdv

Predictive room temperature

Forecast of room temperature

Structure

-

TRPrdv
> Ele0…Ele20

Element0...20

Forecast of room temperature values

Real

0 [°C]
32 [°F]

SpTRPrdv

Predictive room temperature setpoint

Forecast of room temperature setpoint

Structure

-

SpTRPrdv
> Ele0…Ele20

Element0...20

Forecast of room temperature setpoints

Real

0 [°C]
32 [°F]

TiPrdv0...TiPrdv20

Predictive time point 0...Predictive time point 20

Corresponds to the individual values from [TiPrdv].

Real

0

TFlPd0...TFlPd20

Predictive flow temperature setpoint 0...Predictive flow temperature setpoint 20

Corresponds to the individual values from [TFlPrdv].

Real

20.0 [°C]
68.0 [°F]

TOaPd0...TOaPd20

Predictive outside temperature 0...Predictive outside temperature 20

Corresponds to the individual values from [TOaPrdv].

Real

20.0 [°C]
68.0 [°F]

TRPrdv0...TRPrdv20

Predictive room temperature 0...Predictive room temperature 20

Corresponds to the individual values from [TRPrdv].

Real

20.0 [°C]
68.0 [°F]

SpTRPd0...SpTRPd20

Predictive room temperature setpoint 0...Predictive room temperature setpoint 20

Corresponds to the individual values from [SpTRPrdv].

Real

20.0 [°C]
68.0 [°F]

Dstb

Disturbed

Boolean

0

0 - Success reading persistent values.
1 - Error reading persistent values.

SysUnits

System of units

Indicates the system of units used by the block.

Integer

1: International system of units (SI) (fallback)

1...5

1: International system of units (SI) (fallback)
2: International system of units (SI)
3: US system of units
4: Imperial system of units
5: Canadian system of units

ErrCode

Error code indication

Integer

0: No error

= 0 - No error
> 0 - Error codes

Engineering and commissioning

Prerequisites:

  • [EnAda] = 1
  • A (reference) room temperature sensor must be available ([TRSen] = 1).
  • A constant flow of heating medium is required in the reference room (the circulating pump is switched on and no thermostatic valves are operating in the reference room).
  • No fault on the temperature measurements ([ErTR] = [ErTFl] = [ErTOa] = 0).

Adaptation process:

  • After switching on [EnAda] = 1, the building parameters are adapted to the current conditions during an adaptation period of at least one week. The time frame during which an adaptation is conducted can be read in property 'Adaptation time' of the associated BACnet object.
  • The adapted building model parameters are then subjected to an internal block acceptance test. The adaptation states can be viewed on output [AdaSta]. The values as calculated are set to outputs [SpTFlDsO], [SpTFlHiO], [TcnBldgO], [TcnRoomO], [DTRCoefO].
  • The adapted building model parameters can then be used to calculate optimization.

[TkvAda] = 1

The adapted building model parameters are used to calculate optimization.

[TkvAda] = 0

The configured building model parameters calculate optimization, e.g. if the control response does not suffice using the adapted building model parameters.

[ResetAda] = 1

The adaptation process restarts, e.g. if the control response does not suffice using the adapted building model parameters.

Enable and disable adaptation

[EnAda] = 1

Prerequisites:

  • A constant flow of heating medium must be guaranteed in the reference room. The circulating pump is switched on and no thermostatic valves are operating in the reference room.
  • No fault on the temperature measurements ([ErTR] = [ErTFl] = [ErTOa] = 0).

Normal operation:
Building model parameters are adapted continuously.

[TkvAda] = 1

The adapted building model parameters are used to calculate optimization.

[TkvAda] = 0

The configured building model parameters calculate optimization, e.g. if the control response does not suffice using the adapted building model parameters.

[EnAda] = 0

Example: No adaptation wanted or no (reference) room temperature sensor is available ([TRSen] = No).
Example: It may make sense depending on the situation to prevent adaptation during specific times, e.g. when there is a lot of heat gain. It may make sense to operate the adaptation during specific room operating modes, e.g. only if [OpModR] <> Comfort.

Present operating mode

PRDVHCTL supplies the present operating mode in addition to the calculated flow temperature setpoint.

Inactive

PRDVHCTL is switched off ([EnFnct] = 0).

On

Switch on circulating pump

Off

Switch off circulating pump

Boost heating

Boost heating prior to start of room occupancy

Stop

Switch off circulating pump (energy supply) prior to the end of room occupancy

Command

PRDVHCTL is out of service ([OoServ] = 1).

Use estimated room temperature

Estimated room temperature [TREst] can be used as the room model output for other applications, e.g. if no room sensor is available.

Use PRDVHCTL as adaptive heating curve

PRDVHCTL can be used together with HCRV as adaptive heating curve logics.

The following inputs are linked together on PRDVHCTL:

  • The measured temperatures [TR], [TFl], [TOa] and the corresponding error inputs [ErTR], [ErTFl], [ErTOa].
  • The state of the circulating pump [OpSta]

The following settings are required for PRDVHCTL:

  • The function is enabled: [EnFnct] = 1 and [OoServ] = 0.
  • A room temperature sensor is available: [TRSen] = 1.
  • Adaptation is enabled: [EnAda] = 1.
  • The adapted building model parameters must be used: [TkvAda] = 1.

The adapted flow temperature setpoints for the heating curve are linked to HCRV.

  • [SpTFlDsO] is linked to input [SpTFlDs] from HCRV.
  • [SpTFlHiO] is linked to input [SpTFlHi] from HCRV.

The radiator exponent [ExpRad] is not adapted. The configured value is used.

info

The value for outside air temperature [TOaHi] and [TOaDsgn] and the radiator exponent [ExpRad] must be set with the same value on PRDVHCTL and HCRV.

Use external outside air temperature forecast

In the event an external outside air temperature forecast is available for the building site, e.g. a weather service, the forecast can be provided to PRDVHCTL via inputs [ExtTOa0]...[ExtTOa24]. The external forecast is used if [EnExtTOa] = 1. [EnExtTOa] = 0 can be set if an external forecast is unavailable or incorrect. PRDVHCTL switches to an internal forecast for the next optimization.

Inputs [ExtTOa0]...[ExtTOa24] generate a time profile in 1-hour steps. Value [ExtTOa0] represents the outside air temperature forecast for the present time. Value [ExtTOa1] represents the outside air temperature forecast for an hour in the future.

info

A value of [ExtTOa0] is equal to the measured value from [TOa] in an ideal forecast. PRDVHCTL corrects the forecast since this is not the case for a real forecast, e.g. by a weather service. The measured value [TOa] is used as the present forecast and the next forecast values are adapted linearly. The difference between [ExtTOa0] and [TOa] is corrected within the next hour of the forecast. If unwanted, link the measured value [TOa] to [ExtTOa0].

Application

PRDVHCTL optimizes room temperature control of heating applications. It is an alternative to function blocks HCRV (Heating curve), HRA (Heating release algorithm) and OSSC (Optimum start stop control). PRDVHCTL can also be used as an adaptive heating curve.

Troubleshooting

During start-up, PRDVHCTL is initialized with the present values at the inputs. This can have undesired effects if the inputs do not have measured values during start-up (e.g., BACnet references).
To avoid such a situation, PRDVHCTL can be held in inactive state via [EnFnct] until the inputs receive measured values. While PRDVHCTL is in inactive state, it provides the present heating setpoint (selected by [OpModR]) at [SpTFl] and [SpTR] outputs, [EnHDstr] and [PrOpMod] are set with 1 and [TREst] is set with present room temperature [TR].