Integrating Desigo CC in the BACnet/SC network
Desigo CC is integrated on the applicable floor hubs. A separate port must be set up in Desigo CC for each floor hub. This optimizes data traffic between Desigo CC and the floor hubs. Do not integrate the building hub as this would route all data traffic through the building hub and result in data overload.
Create a BACnet/SC network topology building and floor hub

Status of BACnet/SC implementation | ||
|---|---|---|
| BACnet/IP | BACnet/SC compliant |
Building hub | No | Yes |
Basement (Plant hub) | Yes | No |
XWP controller | Yes | No |
1. floor | No | Yes |
2. floor | No | Yes |
Desigo CC | No | Yes |