TX rail properties
The listed properties are displayed in the Hardware and network editor > Inspector window > Properties tab when the TX rail is selected in the Device view tab.
General
Property | Description | Default value |
|---|---|---|
Name | Name of the TX rail. | Depends on other settings. |
Comment | Text field for any helpful information on the automation station. | - |
Rail settings
Property | Description | Default value |
|---|---|---|
Rail length | Defines the length of the TX rail. Range: 160...2000 [mm] | 1000 |
Total width used on rail | Shows the width of the TX rail occupied by devices on the TX rail. Unit: [mm]
| 160 |

Succession of TX devices on TX rails
If more than one TX rail is required, bus connection modules are required. If island bus expansion modules are used, a power supply module is required as well. See the TX-I/O planning and installation manual, CM110562, for the correct place of these devices on the rail and their wiring.
Alarming
Property | Description | Default value |
|---|---|---|
Alarming |
|
|
Bus power supply
Property text | Description | Default value |
|---|---|---|
Bus power supply 1) | The internal bus power supply has to be configured using one of the following settings.
|
|
Total power available | Total power available shows the sum of the powers of the internal power supply of the TX rail and the power supply modules on the TX rail. The value is calculated automatically. Unit: [mA] | 600 |
Power remaining | Power remaining shows the remaining power of the TX rail. The value is calculated automatically, based on the power consumption of the power supply modules and TX modules that consume power. Unit: [mA] Note: | 600 |
1) If the subsystem-specific extension TX-I/O (FldBusMgmt - subsystem-specific extension) of the BACnet object Field bus management object (FldBusMgmt) is enabled, you have to configure this property in the BACnet objects editor or in Web interface.
Internal and external power supply on TX rails
Description | Additional Information | Value |
|---|---|---|
Internal island bus supply DC 24 V | The internal bus supply can typically power 8 TX-I/O modules. See TX-I/O planning and installation manual CM110562 for details. For consumption data of TX devices see table below. | max. 600 mA |
TXS1.12F4 TXS1.12F10 | The internal bus supply can be reinforced by external power supply modules (may be operated in parallel). See TX-I/O planning and installation manual, CM110562 for details. | 1200 mA 1200 mA |
TXS1.EF4 TXS1.EF10 | These are pure island bus connectors and do not supply any power to the modules. | - |
Power consumption of modules on TX rails
Following table shows the consumption data DC 24 V per I/O point and for TX accessories. Values in mA.
Type | TXM… | TXA1.IBE Island bus expansion module | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
16D | 8D | 8U | 8U-ML | 8X | 8X-ML | 8P | 8RB | 8T | 6R | 6R-M | 6RL | 4D3R | ||
Intrinsic consumption 1) | 25 | 25 | 35 | 60 | 30 | 35 | 35 | 25 | 10 | 20 | 30 | 25 | 10 |
|
Maximum consumption of a terminal (Analog input, contact closed, contact open or unconfigured) | 2.5 | 3.5 | 3 | 3 | 25 | 25 | 1 | 8 | 4 | 8 | 8 | 12 | 2/8 |
|
Total consumption | 65 | 53 | 59 | 84 | 230 | 235 | 43 | 89 | 42 | 68 | 78 | 97 | 42 | 50 |
1) Including module status LED.

When calculating the required amount of power, total consumption is always estimated. After assigning the effective data points/signal type, the required power consumption may be reduced.
Power consumption of the TX-IO’s
: Alarming is disabled.
: Alarming is enabled. An Event Enrollment (EE) object is created.
Manual off: Internal bus power supply is permanently off.
Auto detection depending on connected devices: Internal bus power supply is automatically turned off if no TX- I/O modules are connected to the TX rail.