QMX3.P30, P40, P70 properties

The listed properties are displayed in the Hardware and network editor > Inspector window > Properties tab when the device with KNX PL-Link is selected in the Device view tab.

QMX3.P30

QMX3.P40

QMX3.P70

 

 

General and Catalog information

The General and Catalog Information group provides information about the device.

Property

Description

Default value

Mode

Mode shows the network mode of the device. Read only.

KNX PL-Link

Name

Name is a text field to enter the name of the device. The name is used to identify the device in the device view.

Depends on other settings.

Comment

Comment is a free text field to enter any helpful information on the device.

-

Power consumption

Power consumption shows the power the device consumes. Read only.

Unit: [mA]

The value is used to calculate the remaining power of the KNX rail.

See also power consumption and supply on KNX rail of PXC3 or KNX rail of DXR2.

Depends on the device type.

Short designation

Short designation shows a short description of the device. Read only.

Depends on the device type.

Order number

Order number shows the device type. Read only.

Depends on the device type.

Version

Version shows an internal version of the device. Read only.

-

Description

Description shows a short description of the device. Read only.

Depends on the device type.

Device information

The Device information group provides information about the device and settings.

Property text

Description

Default value

Device address (KNX)

Device address (KNX) shows the fixed standard address for devices with KNX PL-Link. Read only.

255

Serial number used

Serial number used defines the method used for device identification.

: The serial number entered in the text field Serial number is used for device identification.

: Device identification has to be done in Web interface. The device has to be in programming mode for Web interface to perform the device identification.

: Device identification has to be done in Web interface.

Serial number

Serial number defines the serial number used for device identification.

Serial number is only enabled and relevant if Serial number used is enabled.

000000000000

RUW Device Object Configuration1)

RUW Device Object Configuration defines if the current air quality level is written to the BACnet object AQualRIndRu and if the information can be used by other devices e.g. QMX3.P36.

Room air quality indication: The current air quality level is written to the BACnet object and the LED for air quality is enabled.

Room air quality indication: The current air quality level is not written to the BACnet object and the LED for air quality is disabled.

Room air quality indication

1) Only available for QMX3.P70

Alarming

Property

Description

Default value

Alarming

: Alarming is disabled.

: Alarming is enabled. An Event Enrollment (EE) object is created.

: Alarming is disabled

Functions

The functions table in the Channel Overview provides an overview of the channels of the device. Depending on the device the values in the table are read only or can be edited. The available types depend on the device and the application function.

Property

Description

Name

Name of the channel. Read only.

Type

Name of the function.

Zone

Part of the geographical address of the device.

Range: 1...126

Room

Part of the geographical address of the device.

Range: 1...63

Subzone

Part of the geographical address of the device.

Range: 1...15

Note
Each channel has to be in a separate subzone.

The functions are described briefly in the table below.

Type

Description

Number of channels used

System

Device information that is mapped to the BACnet object peripheral device (PrphDev). Read only.

1

RTS

Room temperature sensor

1

Some of the functions can be configured. The properties of those functions are described below in order of their appearance in the drop-down list.

Room temperature sensor (RTS)

Property

Description

Default value

Change of value, COV

Change of value, COV defines the change in the value for room temperature that triggers the sending of the value for room temperature.

Range: 0.1...100 [K]

0.1

Heartbeat

Heartbeat defines the time interval to send the value for room temperature if the value for room temperature did not change or the change was smaller than "Change of value, COV".

Range: 120...900 [s]

120

Minimum repetition time

Minimum repetition time defines the minimal time interval before the next value for room temperature can be sent.

Range: 10...60 [s]

10

Relative humidity sensor

Property

Description

Default value

Hum rel COV condition

Hum rel COV condition defines the change in the value for relative humidity that triggers the sending of the value for relative humidity.

Range: 0...10 [%]

5

Hum rel heartbeat

Hum rel heartbeat defines the time interval to report the value for relative humidity if the value did not change or the change was smaller than Hum rel COV condition.

Range 120…900 [s]

900

Hum rel min rep time

Hum rel min rep time defines the minimal time interval before the next value for relative humidity can be sent.

Range: 10...60 [s]

10

Air quality sensor

Property

Description

Default value

AQ COV condition

AQ COV condition defines the change in the value for room air quality that triggers the sending of the value for room air quality.

Range: 0...1000 [ppm]

10

AQ heartbeat

AQ Heartbeat defines the time interval to report the value for air quality if the value did not change or the change was smaller than the AQ COV condition.

Range: 120…900 [s]

900

AQ min rep time

AQ min rep time defines the minimal time interval before the next value for room air quality can be sent.

Range: 10…120 [s]

10

Altitude

Altitude defines the position of the device above sea level.

Range: -200… 3000 [m]

0