QMX3.P02, P34, P37, P44, P74 device properties

The listed properties are displayed in the Hardware and network editor > Inspector window > Properties tab when the device with KNX PL-Link is selected in the Device view tab.

QMX3.P02

QMX3.P34

QMX3.P37

QMX3.P44

QMX3.P74

General and Catalog information

The General and Catalog Information group provides information about the device.

Property

Description

Default value

Mode

Mode shows the network mode of the device. Read only.

KNX PL-Link

Name

Name is a text field to enter the name of the device. The name is used to identify the device in the device view.

Depends on other settings.

Comment

Comment is a free text field to enter any helpful information on the device.

-

Power consumption

Power consumption shows the power the device consumes. Read only.

Unit: [mA]

The value is used to calculate the remaining power of the KNX rail.

See also power consumption and supply on KNX rail of PXC3 or KNX rail of DXR2.

Depends on the device type.

Short designation

Short designation shows a short description of the device. Read only.

Depends on the device type.

Order number

Order number shows the device type. Read only.

Depends on the device type.

Version

Version shows an internal version of the device. Read only.

-

Description

Description shows a short description of the device. Read only.

Depends on the device type.

Device information

The Device information group provides information about the device and settings.

Property

Description

Default value

Device address (KNX)

Device address (KNX) shows the fixed standard address for devices with KNX PL-Link. Read only.

255

Network address (KNX)

Network address (KNX) shows the network address that was assigned based on the device address (KNX). Read only.

0.2.255

Serial number used

Serial number used defines the method used for device identification.

: The serial number entered in the text field Serial number is used for device identification.

: Device identification has to be done in Web interface. The device has to be in programming mode for Web interface to perform the device identification.

: Device identification has to be done in Web interface.

Serial number

Serial numberis a text field to enter the serial number used for device identification.

Serial number is only enabled and meaningful if Serial number used is enabled.

000000000000

Customized view

Customized view defines which of the QMX3 templates from the project tree is used.

List of available templates

<Select customized view>

Alarming

Property

Description

Default value

Alarming

: Alarming is disabled.

: Alarming is enabled. An Event Enrollment (EE) object is created.

: Alarming is disabled

Functions

The functions table in the Channel Overview provides an overview of the channels of the device. Depending on the device the values in the table are read only or can be edited. The available types depend on the device and the application function.

Property

Description

Name

Name of the channel. Read only.

Type

Name of the function.

Zone

Part of the geographical address of the device.

Range: 1...126

Room

Part of the geographical address of the device.

Range: 1...63

Subzone

Part of the geographical address of the device.

Range: 1...15

Note
Each channel has to be in a separate subzone.

Activate

Activate defines if the channel is activated.

: The channel is activated.

: The channel is deactivated and is not considered in the calculation of the limiting factors of the automation station.

The functions are described briefly in the table below. The assortment of functions depends on the device.

Type

Description

Number of channels used

GPDO

General purpose digital output. Read only.

1

HVAC

Heating, ventilating, and air conditioning. Read only.

1

LDSB

Light dimming sensor basic. Read only.

1

SSSB

Sunblind sensor basic. Read only.

1

Some of the functions can be configured. The properties of those functions are described below in alphabetical order.

Outside sensor zone

The outside sensor zone is supported by QMX3.P34, QMX3.P37, QMX3.P44 and QMX3.P74.

Property

Description

Default value

Outside sensor zone

Outside sensor zone defines which outside sensors provide data to the room operator unit.

Outside sensors are assigned to outside sensor zones instead of geographical addresses (building zone, room, subzone).

Range: 1...31

Depends on other settings.