Switching actuators properties

The listed properties are displayed in the Hardware and network editor > Inspector window > Properties tab when the device with KNX PL-Link is selected in the Device view tab.

N 530D31
N 532D31
N 534D31

N 530D51
N 532D51
N 534D51

N 534D61
N 534D61
N 534D61

N 535D51

 


 

RL 512/23
JB 512C23

RL513/23
JB 513C23

RS 510/23
JB 510C23

UP 510/03

UP 510/13

General and Catalog information

The General and Catalog Information group provides information about the device.

Property

Description

Default value

Mode

Mode shows the network mode of the device. Read only.

KNX PL-Link

Name

Name is a text field to enter the name of the device. The name is used to identify the device in the device view.

Depends on other settings.

Comment

Comment is a free text field to enter any helpful information on the device.

-

Power consumption

Power consumption shows the power the device consumes. Read only.

Unit: [mA]

The value is used to calculate the remaining power of the KNX rail.

See also power consumption and supply on KNX rail of PXC3 or KNX rail of DXR2.

Depends on the device type.

Short designation

Short designation shows a short description of the device. Read only.

Depends on the device type.

Order number

Order number shows the device type. Read only.

Depends on the device type.

Version

Version shows an internal version of the device. Read only.

-

Description

Description shows a short description of the device. Read only.

Depends on the device type.

Device information

Property text

Description

Default value

Device address (KNX):

Device address (KNX) shows the fixed standard address for devices with KNX PL-Link. Read only.

255

Serial number used

Serial number used defines the method used for device identification.

: The serial number entered in the text field Serial number is used for device identification.

: Device identification has to be done in Web interface. The device has to be in programming mode for Web interface to perform the device identification.

: Device identification has to be done in Web interface.

Serial number

Serial number defines the serial number used for device identification.

Serial number is only enabled and relevant if Serial number used is enabled.

000000000000

 

Alarming

Property

Description

Default value

Alarming

: Alarming is disabled.

: Alarming is enabled. An Event Enrollment (EE) object is created.

: Alarming is disabled

Functions

The functions table in the Channel Overview provides an overview of the channels of the device. Depending on the device the values in the table are read only or can be edited. The available types depend on the device and the application function.

Property

Description

Name

Name of the channel. Read only.

Type

Name of the function.

Zone

Part of the geographical address of the device.

Range: 1...126

Room

Part of the geographical address of the device.

Range: 1...63

Subzone

Part of the geographical address of the device.

Range: 1...15

Note
Each channel has to be in a separate subzone.

Activate

Activate defines if the channel is activated.

: The channel is activated.

: The channel is deactivated and is not considered in the calculation of the limiting factors of the automation station.

The functions are described briefly in the table below.

Type

Description

Number of channels used

System

Device information that is mapped to the BACnet object peripheral device (PrphDev). Read only.

1

Some of the functions can be configured. The properties of those functions are described below in order of their appearance in the drop-down list.

Light switching actuator basic LSAB

Property text

Description

Default value

Power return mode

Power return mode defines the behavior of the light when power returns after a power failure or when the application is restarted.

off: The lights are off.

on: The lights are on.

no change (meaningful for bistable relay output): The actuator keeps the switching state of the moment of power failure.

not allowed

last (saved value at power down): The light goes to the value saved at power down.

off

Power failure mode

Power failure mode defines the behavior of the actuator if the power fails.

off: The actuator is switched off.

on: The actuator is switched on.

no change: The actuator keeps the actual value.

off

Prio forced control

Prio forced control sets the priority for forced control commands.

Range: 1...16

6

Blink On-time

Blink Off-time and Blink On-time define the blinking frequency for the blink warning function.

The Blink On-time defines how long the light will be switched on.

Range: 0...50 [0.1 s]

0 [0.1 s]: The blink warning function is disabled.

10

Blink Off-time

Blink Off-time and Blink On-time define the blinking frequency for the blink warning function.

The Blink Off-time defines how long the light will be switched off.

Range: 0...50 [0.1 s]

0 [0.1 s]: The blink warning function is disabled.

2