[Ahu21] Air handling unit, temperature cascade control, pressure control

Plant example Ahu21 has speed-controlled fans, chilled water cooling coil, hot water heating coil, energy recovery with a rotary heat exchanger, and shutoff dampers.

Functions

Plant diagram

Components

Components and functions

Components and functions of the plant example:

Component

Function

BACnet object

Fire detection contact

Switches the plant off.

[BI] Fire detection contact

Operating mode switch

Switches the plant to: Auto | Off | On

[MI] Operating mode switch

 

Manual operating mode selection

Switches the plant to: Auto | Off | On

[MCnfVal] Manual operating mode selection

Scheduler program

Switches the plant to: Off | On

[MSchedule] Scheduler

 

Present operating mode

Reports the present operating mode: Off | On

Plant operating modes and control sequence

[MCalcVal] Present operating mode

 

Reason for present operating mode

Reports the reason for the present operating mode: Exception | Operating mode switch | Manual operating mode selection | Scheduler | Switching action operating

[MCalcVal] Reason for present operating mode

 

Temperature control basic setpoints (1)

Setpoints for upper and lower room temperature

Function diagram for temperature control basic setpoints (1)

[ACnfVal] Setpoint for cooling

[ACnfVal] Setpoint for heating

 

Seasonal temperature compensation (2)

Corrects the high and low room temperature setpoint per the outside temperature.

Function diagram for seasonal temperature compensation (2)

[BCalcVal] Seasonal temperature compensation

 

Temperature cascade control (3)

(Room/supply air temperature cascade)

Calculates the high and low supply air setpoint per the outside temperature.

Function diagram for temperature cascade control (3)

Temperature control (Folder)

> [ACalcVal] Present setpoint high for room temperature

> [ACalcVal] Present setpoint low for room temperature

> [ACalcVal] Present setpoint high for supply air temperature

> [ACalcVal] Present setpoint low for supply air temperature

> [ACnfVal] Gain

> [ICnfVal] Integral action time Tn

> [ACnfVal] Minimum supply air temperature setpoint

> [ACnfVal] Maximum supply air temperature setpoint

Room temperature sensor

Measures room temperature.

[AI] Room temperature

Exhaust air differential pressure sensor

Measures the differential pressure between duct and environment.

[AI] Extract air pressure

(Located in Exhaust air fan)

Supply air differential pressure sensor

Measures the differential pressure between duct and environment.

[AI] Supply air pressure

(Located in Supply air fan)

Extract air temperature sensor

Measures extract air temperature.

[AI] Extract air temperature

Supply air temperature sensor

Measures the supply air temperature.

[AI] Supply air temperature

Supply air fan

Supply air fan (Folder)

Pressure controller

Controls the supply air pressure.

Function diagram for supply air pressure control

> [Controller] Pressure controller

 

Supply air pressure setpoint

Determines the setpoint for supply air pressure.

> [ACnfVal] Setpoint supply air pressure

 

Command

Switches on/off the fan as needed.

> [BO] Command

Speed

Controls the fan speed between 0 and 100 [%].

> [AO] Speed

Maintenance switch

Switches off the fan and the plant.

The fan outputs are blocked locally at a high priority (Prio 2).

> [BI] Maintenance switch

Fault message

Fault messages, e.g. from the external motor control (variable speed drives).

Switches off the fan and the plant.

> [BI] Fault

Cooling coil

Cooling coil (Folder)

 

Reports chilled water demand to cooling distribution.

> [BCalcVal] Chilled water demand

Valve

Valve (Folder)

Temperature controller

Controls the supply air temperature.

Function diagram for supply air temperature control

> [Controller] Temperature controller

Valve position

Controls the valve position: 0…100 [%]

> [AO] Position

Heating coil

 

Heating coil (Folder)

 

Reports hot water demand to heat distribution.

> [BCalcVal] Hot water demand

Frost protection

Prevents the hot water heating coil from freezing.

If the frost protection monitor triggers:

  • The plant switches off.
  • The valve fully opens (100%) and the pump is also switched on. Both at high priority (Prio 4).

> [BI] Frost protection monitor

Purge optimization

Purges the heating coil with hot water at cold outside temperature prior to switching on fans.

Duration and valve opening are optimized using function [PURGE] purge optimization.

[PURGE] Purge optimization

> [BCalcVal] Startup purge active

Pump

Pump (Folder)

Pump command

Switches on/off the pump as needed.

> [BO] Command

Pump run when the outside air temperature is low:

Pump always operates at low outside temperatures (frost protection).

 

Kick function (pump kick)

Prevents the pump from seizing during long idle periods.

[KICKFNCT] Kick function

 

Valve

Valve (Folder)

Temperature controller

Controls the supply air temperature.

Function diagram for supply air temperature control

> [Controller] Temperature controller

Valve position

Controls the valve position: 0…100 [%]

> [AO] Position

Extract air filter

Extract air filter (Folder)

Monitors the differential pressure through the extract air filter and reports a dirty filter.

> [BI] Filter detector

Energy recovery

(Rotary heat exchanger)

Reuses sensitive and latent energy from extract air for the supply air through the transfer of heat and humidity.

Changeover of heating/cooling:

Determines whether it can be heated or cooled using extract air:

  • Energy recovery can be used to heat if the extract air temperature is higher than the outside temperature.
  • Energy recovery can be used to cool if the extract air temperature is lower than the outside temperature.

Energy recovery (Folder)

Temperature controller

Controls the supply air temperature.

The supply air setpoint is the result of the average of the high setpoint for supply air temperature and the low setpoint for supply air temperature.

Function diagram for supply air temperature control

> [Controller] Temperature controller

Speed

Controls the speed of the rotary heat exchanger: 0…100 [%]

> [AO] Speed

Anti-icing protection

The temperature sensor measures the exhaust air temperature after energy recovery.

The anti-icing protection controller holds the exhaust air temperature sufficiently high by lowering the power (speed). Prevents freezing of any condensation and icing on the exchanger surface.

> [AI] Exhaust air temperature after energy recovery

> [Controller] Anti-icing protection controller

Reports faults from external energy recovery control.

> [BI] Fault

Outside air filter

Outside air filter (Folder)

Monitors the differential pressure through the outside air filter and reports a dirty filter.

> [BI] Filter detector

Exhaust air fan

Exhaust air fan (Folder)

Pressure controller

Controls extract air pressure.

Function diagram for extract air pressure control

> [Controller] Pressure controller

 

Determines the extract air pressure setpoint.

> [ACnfVal] Setpoint extract air pressure

 

Command

Switches on/off the fan as needed.

> [BO] Command

Speed

Controls the fan speed: 0…100 [%]

> [AO] Speed

 

Maintenance switch

Switches off the fan and the plant.

The fan outputs are blocked locally at a high priority (Prio 2).

> [BI] Maintenance switch

Fault message

Fault messages, e.g. from the external motor control (variable speed drives).

Switches off the fan and the plant.

> [BI] Fault

Outside air damper

Outside air damper (Folder)

Command

Opens and closes the outside air damper.

Adjustable damper runtime in the program.

> [BO] Command

Exhaust air damper

Exhaust air damper (Folder)

Command

Opens and closes the exhaust air damper.

Adjustable damper runtime in the program.

> [BO] Command

Sensor for outside temperature

Measures outside temperature.

> [AI] Outside air temperature

Functions and diagrams

Overview

Room/supply air temperature cascade control with seasonal temperature compensation:

Key

1

 

SpH

Setpoint for heating

SpC

Setpoint for cooling

2

 

HiCorr

High correction value

LoCorr

Low correction value

CHAR_LIN

Characteristics with linearization

SsnCmpT

Seasonal temperature compensation

3

 

PrSpLoTSu

Present setpoint low for supply air temperature

PrSpHiTSu

Present setpoint high for supply air temperature

CasCtr

Cascade controller

PrSpLoT

Present setpoint low for room temperature

PrSpHiT

Present setpoint high for room temperature

TCtl

Temperature control

4

 

Erc

Energy recovery

Hcl

Heating coil

Ccl

Cooling coil

Actg =1

Control action for the rotary heat exchanger is heating.

Actg =0

Control action for the rotary heat exchanger is cooling.

Spd

Speed

Vlv-Pos

Valve position

TCtr

Temperature controller

Avrg

Average

Plant example Ahu21 is used as room/supply air temperature cascade control.

Ahu21 can be adapted to the following applications with just a few modifications:

  • Extract air/supply air temperature cascade control
  • Pure supply air temperature control
  • Pure room temperature control

Ventilation control by extract air, supply air, or room temperature for flat plants

Temperature control basic setpoints (1)

Basic setpoints, that, for example, are operated by the operator:

BACnet objects

Name

Description

Object type

Default value

SpC

Setpoint for cooling

ACnfVal

24 [°C]

SpH

Setpoint for heating

ACnfVal

21 [°C]

This plant example deals with basic setpoint for temperature control of the room setpoints.

Seasonal temperature compensation (2)

Seasonal temperature compensation corrects the high and low room temperature setpoint per the outside temperature.

The correction begins on the outside temperature start point [TOa...SttPnt] and ends with the outside temperature end point [TOa...EndPnt]. [Sp…CorrEndPnt] determines the height of the correction.

Key

PrSpShftHi

Present setpoint shift high

SpHiCorrEndPnt

High correction value at the outside air end point

CHAR_LIN

Characteristics with linearization

TOaHiEndPnt

Outside air temperature high for end point

TOaHiSttPnt

Outside air temperature high for start point

TOa

Outside air temperature

PrSpShftLo

Present setpoint shift low

SpLoCorrEndPnt

Low correction value at the outside air end point

TOaLoEndPnt

Outside air temperature low for end point

TOaLoSttPnt

Outside air temperature low for start point

BACnet objects

Name

Description

Object type

Default value

SsnCmpT

Seasonal temperature compensation

The seasonal temperature compensation is active if a correction is not equal to zero.

BCalcVal

Inactive

Set values on function block CHAR_LIN

Name

Description

Default value

TOaHiSttPnt

Outside air temperature high for start point (X1 on CHAR_LIN)

Outside temperature at which the temperature compensation increases the high setpoint.

26 [°C]

TOaHiEndPnt

Outside air temperature high for end point (X2 on CHAR_LIN)

Outside temperature up to which the temperature compensation increases the high setpoint.

32 [°C]

SpHiCorrEndPnt

High correction value at the outside temperature end point = > Height of the correction (Y2 on CHAR_LIN)

3 [K]

TOaLoSttPnt

Outside air temperature low for start point (X1 on CHAR_LIN)

Outside temperature at which the temperature compensation increases the low setpoint.

26 [°C]

TOaLoEndPnt

Outside air temperature low for end point (X2 on CHAR_LIN)

Outside temperature up to which the temperature compensation increases the low setpoint.

32 [°C]

SpLoCorrEndPnt

Low correction value at the outside temperature end point = > Height of the correction (Y2 on CHAR_LIN)

1 [K]

Combination of basic setpoints (1) and seasonal temperature compensation (2)

Key

SpTR

Room temperature setpoint

PrSpHiT

Present setpoint high for room temperature

PrSpShftHi

Present setpoint shift high

PrSpLoT

Present setpoint low for room temperature

PrSpShftLo

Present setpoint shift low

TOa

Outside air temperature

BACnet objects

Name

Description

Object type

Default value

PrSpHiT

Present setpoint high for room temperature

The present setpoint high room temperature or extract air setpoint for cooling operation as corrected by the seasonal temperature compensation

ACalcVal

23 [°C]

PrSpLoT

Present setpoint low for room temperature

The present setpoint low room temperature or extract air setpoint for heating operation as corrected by the seasonal temperature compensation

ACalcVal

22 [°C]

Comfort for the room is defined using the two basic setpoints for the room temperature; both of which are compensated to account for outside temperature.

Temperature cascade control (3)

Temperature cascade control of the room supply air calculates the high and low supply air temperature setpoint as per the room temperature.

Function block CAS_CTR calculates the following setpoints:

  • [PrSpHiTSu] Present setpoint high for supply air temperature
  • [PrSpLoTSu] Present setpoint low for supply air temperature

[CAS_CTR] Cascade controller

The supply air setpoints [PrSpLoTSu] and [PrSpHiTSu] are limited on the low side by the minimum supply air temperature setpoint [SpTSuMin] and by the maximum supply air temperature setpoint [SpTSuMax] on the high side.

If the room temperature [TR] exceeds the present setpoint high for the room temperature [PrSpHiT], the present setpoint high for supply air [PrSpHiTSu] is continuously reduced until the minimum setpoint low for supply air [SpTSuMin] is reached.

If the room temperature [TR] drops below the present setpoint low for room temperature [PrSpLoT], the present setpoint low for supply air [PrSpLoTSu] is continuously increased until the maximum setpoint for supply air [SpTSuMax] is reached.

Setpoints are forwarded to the components responsible for supply air temperature control (4).

The setpoint for energy recovery with rotary heat exchanger is calculated using the average of [PrSpHiTSu] and [PrSpLoTSu].

Key

TSu

Supply air temperature

SpTSuMax

Maximum supply air temperature setpoint

PrSpLoTSu

Present setpoint low for supply air temperature

PrSpHiTSu

Present setpoint high for supply air temperature

SpTSuMin

Minimum supply air temperature setpoint

PrSpLoT

Present setpoint low for room temperature

PrSpHiT

Present setpoint high for room temperature

TR

Room temperature

BACnet objects

Name

Description

Object type

Default value

PrSpHiT

Present setpoint high for room temperature

The present setpoint high room temperature or extract air setpoint for cooling operation as corrected by the seasonal temperature compensation

ACalcVal

23 [°C]

PrSpLoT

Present setpoint low for room temperature

The present setpoint low room temperature or extract air setpoint for heating operation as corrected by the seasonal temperature compensation

ACalcVal

22 [°C]

PrSpHiTSu

Present setpoint high for supply air temperature

Calculated supply air setpoint for cooling

ACalcVal

18 [°C]

PrSpLoTSu

Present setpoint low for supply air temperature

Calculated supply air setpoint for heating

ACalcVal

18 [°C]

SpTSuMax

Maximum supply air temperature setpoint

Limits supply air on the high side.

ACnfVal

32 [°C]

SpTSuMin

Minimum supply air temperature setpoint

Limits supply air on the low side.

ACnfVal

15 [°C]

Gain

Gain

Gain factor for the cascade controller

ACnfVal

3 [K/K]

Tn

Integral action time Tn

Integral action time for the cascade controller

ICnfVal

1200 [s]

Supply air temperature control (4)

Key

Vlv'Pos, Spd

Position, speed

Actg =1

Control action for the rotary heat exchanger is heating.

Actg =0

Control action for the rotary heat exchanger is cooling.

Hcl'Vlv'Pos

Heating coil valve position

Ccl'Vlv'Pos

Cooling coil valve position

Erc'Spd

Speed of energy recovery with rotary heat exchanger speed

PrSpLoTSu

Present setpoint low for supply air temperature

PrSpHiTSu

Present setpoint high for supply air temperature

TSu

Supply air temperature

BACnet objects

Name

Description

Object type

Default value

Hcl'Vlv'TCtr

Temperature controller for heating coil

Controls the supply air temperature.

Controller

N/A

The temperature controller acts as a PI controller (PID with derivative action time Tv=0) and compares the temperature setpoint [SpTSu] against the supply air temperature [TSu] and calculates the valve position [Hcl'Vlv'Pos] on the output.

The following controller variables are preset:
- Controller gain: 5 [%/K]
- Integral action time Tn: 180 [s]

The controller is locked in the following cases:
- High outside temperature

Erc'TCtr

Temperature controller for energy recovery

Controls the supply air temperature.

Controller

N/A

Conditions for heating are fulfilled:
The temperature controller acts as a PI controller (PID with derivative action time Tv=0) and compares the temperature setpoint (average of [PrSpHiTSu] and [PrSpLoTSu]) against the supply air temperature [TSu] and calculates the speed [Erc'Spd] on the output.

The following controller variables are preset:
- Controller gain: 5 [%/K]
- Integral action time Tn: 180 [s]

Conditions for cooling are fulfilled:
The temperature controller changes over to a 2-position controller (CtlMod = 2-position control) and compares the temperature setpoint (average of [PrSpHiTSu] and [PrSpLoTSu]) against the supply air temperature [TSu] and calculates the speed [Erc'Spd] on the output. The speed in this case switches between 0 and 100 [%].

The following controller variables are preset:
- Hysteresis [SwiOnHys]: 0.5 [K]
- Hysteresis [SwiOffHys]: 0.5 [K]
- Delay [SwiDly]: 5 [s]

Behavior at plant startup:

Ramp-up at low outside temperature and if purge optimization [PURGE] occurred:
Energy recovery is started at 100% and the temperature controller-heating coil immediately assumes temperature control.

Ramp-up if no purge optimization [PURGE] occurred:
Temperature controller-energy recovery is normally enabled and assumes temperature control.

Ccl'TCtr

Temperature controller for cooling coil

Controls the supply air temperature.

Controller

N/A

The temperature controller acts as a PI controller (PID with derivative action time Tv=0) and compares the temperature setpoint [PrSpHiTSu] against the supply air temperature [TSu] and calculates the valve position [Ccl'Vlv'Pos] on the output.

The following controller variables are preset:
- Controller gain: 5 [%/K]
- Integral action time Tn: 180 [s]

The controller is locked in the following cases:
- Low outside temperature

Icing protection on energy recovery with rotary heat exchangers

Holds the exhaust air temperature sufficiently high by lowering the power (speed).

Prevents:

  • Freezing of any condensation
  • Icing of the exchanger surface

BACnet objects

Name

Description

Object type

Default value

Erc'lcPrtCtr

Anti-icing protection controller

Prevents icing on the exchanger surface.

Controller

N/A

The anti-icing protection controller acts as a PI controller (PID with derivative action time Tv=0) and compares the temperature setpoint set on input [Sp] against the exhaust air temperature after energy recovery [TEhAfErc] and calculates value [YCtrMax] on the output on BACnet object Erc'TCtr (temperature controller for energy recovery).

The following controller variables are preset:
- Controller gain: 20 [%/K]
- Integral action time Tn: 120 [s]

Supply air pressure control

Controls the supply air pressure using the supply air fan.

Key

Spd, PrVal

Speed, Present value

SpdMax

Maximum speed

SpdMin

Minimum speed

SpP

Pressure setpoint

P

Pressure

BACnet objects

Name

Description

Object type

Default value

FanSu'PCtr

Pressure controller for supply air fan

Controls the supply air pressure.

Controller

N/A

The pressure controller acts as a PI controller (PID with derivative action time Tv=0) and compares the setpoint for supply air pressure [SpPSu] against the supply air pressure [PSu] and calculates the fan speed [Spd] on the output.

The following controller variables are preset:
- Controller gain: 0.2 [%/Pa]
- Integral action time Tn: 60 [s]

Extract air pressure controller

Controls the extract air pressure using an exhaust air fan.

Key

Spd, PrVal

Speed, Present value

SpdMax

Maximum speed

SpdMin

Minimum speed

SpP

Pressure setpoint

P

Pressure

BACnet objects

Name

Description

Object type

Default value

FanEh'PCtr

Pressure controller for exhaust air fan

Controls extract air pressure.

Controller

N/A

The pressure controller acts as a PI controller (PID with derivative action time Tv=0) and compares the setpoint for extract air pressure [SpPEx] against the extract air pressure [PEx] and calculates the fan speed [Spd] on the output.

The following controller variables are preset:
- Controller gain: 0.2 [%/Pa]
- Integral action time Tn: 60 [s]

Plant operating modes and control sequence

Plant operating modes:

  • Off (1)
  • On (2)

The operating modes are reported on [MCalcVal] object 'Present operating mode'.

At the same time, the reason for the present operating mode is reported to another [MCalcVal] object:

  • Exception (1)
  • Operating mode switch (2), resulting from an active (not equal to Auto) operating mode switch
  • Manual operating mode selection (3), resulting from an active (not equal to Auto) manual operating mode selection
  • Scheduler (4), resulting from an active scheduler
  • Switching action is performed (5) and is the result of a transition state on the plant (e.g. longer switch-off due to a delay to dry out the cooler)

The components for control are connected to function block CMDSEQ_B and are also acquired by this function block. See table below.
[CMDSEQ_B] Command sequence for binary

There is a normal mode and exception mode.

Normal operation

Sources for normal mode:

  • [MI] Operating mode switch
  • [MCnfVal] Manual operating mode selection
  • [MSchedule] Scheduler

In normal mode, the components are controlled at priority 15 per the operating mode, sequence, and function in function block CMDSEQ_B. The set timeouts and/or delays are considered.

Exception mode

Sources for exception mode:

  • Fire detection contact
  • Faults in the components, e.g. fault contact, frost protection monitor, maintenance switch

In exception mode, all outputs are switched off directly at priority 5 and the present operating mode is set to 'Off'. This is reported to function block CMDSEQ_B on input [RpdOff] and the components are switched off immediately as of the function block at priority 15.

The set timeouts and/or delays are not considered.

Special case frost protection:

In this case, outputs [AO] valve position and [BO] pump command are switched on by the heating coil at priority 4.

Special case maintenance switch:

In this case, outputs [AO] speed and [BO] command are switched off by the fans at priority 2.

Components, sequence, and function in CMDSEQ_B

Plant operating mode

Component

 

Hcl

DmpOa

DmpEh

Erc

FanSu

FanEh

Ccl

Off

Off

Off

Off

Off

Off

Off

Off

On

On

On

On

On

On

On

On

 

Sequences

 

Start sequence

1

2

2

3

3

3

3

Start function

Feedback or Timeout

AND (Group with next aggregate)

Feedback and delay

AND (Group with next aggregate)

AND (Group with next aggregate)

AND (Group with next aggregate)

AND (Group with next aggregate)

Start delay

5m

-

2m

-

-

-

-

 

Stop sequence

3

3

3

2

2

2

1

Stop function

AND (Group with next aggregate)

AND (Group with next aggregate)

AND (Group with next aggregate)

Delay

AND (Group with next aggregate)

AND (Group with next aggregate)

Feedback or Timeout

Stop delay

-

-

-

1m

-

-

5m

Start sequence

  1. The heating coil switches on.
    It is further switched if an operating message from the heating coil arrives on the input pin for CMDSEQ_B or, at the latest after 2 minutes (function Timeout).
  2. The shutoff dampers switch on at the same time (function AND).
  3. In this plant example, the shutoff dampers do not have an end switch. The operating message is formed based on the commands and sent immediately. This ensures that the dampers are open, that it waits for 2 minutes, and only then switches.
  4. The fans, energy recovery, and cooling coil switch on at the same time (function AND).

Stop sequence

  1. The cooling coil switches off.
    It is further switched if an operating message (Off) from the component arrives on the input pin for CMDSEQ_B or, at the latest after 5 minutes (function Feedback or Timeout).
    When switching off the corresponding components (cooling coil), the operating message (On) is maintained up to 5 minutes so that it can dry out, if it was operating. If it is not operating, its operating message is immediately set to Off without a delay to the stop sequence
  2. The fans and energy recovery switch off at the same time (function AND). It waits for 2 minutes (function Delay).
  3. The shutoff dampers close and the cooling coil switches off (function AND).
Start-up control and alarm handling

Start-up control (nested chart SttUpAlmHdl)

The following functionality is available for an automatic startup of the plant, e.g. after a loss of power and return of power:

  1. Fixed switch-on delay (can be set on input pin [DlySttUp])
  2. The plant remains off to ensure communications are reliable and cross-check references are triggered. 'Exception' is reported as the reason for the present operating mode.
  3. Automatic acknowledge (2x) of possible pending alarms during a fixed switch-on delay.
  4. Additional adjustable delay for staged plant ramp-up (can be set on input pin [DlyOn])

Alarm handling (nested chart SttUpAlmHdl)

The state of events on the plant is acquired by BACnet object 'Plant state'. The state is mapped on function block CMN_EVT.
[CMN_EVT] Common event

The following functions are available:

  1. Automatic acknowledge (2x) after startup
  2. Alarm acknowledgement with a value object
  3. Alarm indication:
    - For pending alarms On
    - For unprocessed alarms flashing
  4. Ability to connect the acknowledge button [BI]
  5. Ability to connect to an alarm indication [BO], e.g. an alarm lamp through an output block [BO]
  6. Ability to connect to other alarm handling functions on other plants, e.g. acknowledge button and alarm indication for multiple plants in the same control cabinet

Startup function and alarm handling for flat plants

I/O data points

Name

Description

Type

Signal/connection

State text

Engineering unit

FireDetCont

Fire detection contact

Alarm function: Extended (Notification class 7)

Reference value: Tripped

Time deviation: 0 [s]

BI

NC contact

Normal | Tripped

N/A

OpModSwi

Operating mode switch

MI

N/A

Auto | Off | On

N/A

TR

Room temperature

AI

LG-Ni1000

N/A

0...50 [°C]

FanEh'PEx

Exhaust air fan extract air pressure

AI

0...10 [V]

N/A

0...500 [Pa]

FanSu'PSu

Supply air fan supply air pressure

AI

0...10 [V]

N/A

0...500 [Pa]

TEx

Extract air temperature

AI

LG-Ni1000

N/A

0...50 [°C]

TSu

Supply air temperature

AI

LG-Ni1000

N/A

0...50 [°C]

FanSu'Spd

Supply air fan speed

AO

0...10 [V]

N/A

0...100 [%]

FanSu'Cmd

Supply air fan command

BO

NO contact

Off | On

N/A

FanSu'MntnSwi

Supply air fan maintenance switch

Alarm function: Basic (Notification class 8)

Reference value: Maintenance

Time deviation: 0 [s]

BI

NO contact

Normal | Maintenance

N/A

FanSu'Flt

Supply air fan fault

Alarm function: Basic (Notification class 8)

Reference value: Tripped

Time deviation: 0 [s]

BI

NO contact

Normal | Tripped

N/A

Ccl'Vlv'Pos

Cooling coil valve position

AO

0...10 [V]

N/A

0...1000 [%]

Hcl'Vlv'Pos

Heating coil fan position

AO

0...10 [V]

N/A

0...100 [%]

Hcl'Pu'Cmd

Heating coil pump command

BO

NO contact

Off | On

N/A

Hcl'FrPrtMon

Frost protection monitor

Alarm function: Extended (Notification class 7)

Reference value: Tripped

Time deviation: 0 [s]

BI

NC contact

Normal | Tripped

N/A

FilEx'FilDet

Extract air filter detector

BI

NO contact

Normal | Tripped

N/A

Erc'Spd

Energy recovery speed

AO

0...10 [V]

N/A

0...100 [%]

Erc'Flt

Energy recovery fault

Alarm function: Basic (Notification class 8)

Reference value: Tripped

Time deviation: 0 [s]

BI

NO contact

Normal | Tripped

N/A

Erc'TEhAfErc

Energy recovery exhaust air temperature after heat exchanger

AI

LG-Ni1000

N/A

0...50 [°C]

FilOa'FilDet

Outside air filter detector

BI

NO contact

Normal | Tripped

N/A

FanEh'Spd

Exhaust air fan speed

AO

0...10 [V]

N/A

0...100 [%]

FanEh'Cmd

Exhaust air fan command

BO

NO contact

Off | On

N/A

FanEh'MntnSwi

Exhaust air fan maintenance switch

Alarm function: Basic (Notification class 8)

Reference value: Maintenance

Time deviation: 0 [s]

BI

NO contact

Normal | Maintenance

N/A

FanEh'Flt

Exhaust air fan fault

Alarm function: Basic (Notification class 8)

Reference value: Tripped

Time deviation: 0 [s]

BI

NO contact

Normal | Tripped

N/A

DmpOa'Cmd

Outside air damper command

BO

NO contact

Close | Open

N/A

DmpEh'Cmd

Exhaust air damper command

BO

NO contact

Close | Open

N/A

TOa

Outside temperature

AI

LG-Ni1000

N/A

-70...70 [°C]