[Dhw23] Domestic hot water, direct domestic hot water treatment

Plant example Dhw23 is a plant for domestic hot water handling.

Functions

Plant diagram

Components

Components and functions

Components and functions of the plant example:

Component

Function

BACnet object

Scheduler program

Switches the plant to operating mode: Off | On

[MSchedule] Scheduler

Operating mode switch

Switches the plant to: Auto | Off | On

[MI] Operating mode switch

 

Manual operating mode selection

Switches the plant to: Auto | Off | On

[MCnfVal] Manual operating mode selection

 

Present operating mode

Reports the present operating mode: Off | On

Plant operating modes and control sequence

[MCalcVal] Present operating mode

 

Reason for present operating mode

Reports the reason for the present operating mode: Exception | Operating mode switch | Manual operating mode selection | Scheduler

[MCalcVal] Reason for present operating mode

Flow detector

Reports flow: No flow | Flow

The control valve is precontrolled, for example, to 25% if flow is reported.

[BI] Flow detector

Circulating pump

Circulating pump (Folder)

Command

Switches on/off the pump as needed.

> [BO] Command

The circulating pump is enabled if the plant is switched on. The plant operates in interval operation, e.g. 10 minutes on, 20 minutes off.

The circulating pump is enabled without interruption if the function for legionella prevention is active.

Scalding protection

Protects the consumer against water that is too hot.

Scalding protection (Folder)

Hot water temperature consumer side

Measures the temperature of hot water to the consumer.

[AI] Consumer hot water temperature

Temperature controller

Limits the hot water temperature to the consumers.

[Controller] Temperature controller

Positioning

0% = Bypass

100% = Through-port

[AO] Position

Hot water temperature sensor

Measures the temperature at the heat exchanger outlet.

[AI] Hot water temperature

Hot water temperature setpoint

Setpoint for the desired hot water temperature

[ACnfVal] Hot water temperature setpoint

Present hot water temperature setpoint

Displays the present setpoint for the hot water temperature. The value is higher compared to the normal hot water temperature setpoint if the function for legionella prevention is active.

[ACalcVal] Present hot water temperature setpoint

Legionella prevention

Protects hot water against legionella.

Legionella prevention (Folder)

Scheduler program

Scheduler for legionella prevention

> [BSchedule] Scheduler

Setpoint

[ACnfVal] Setpoint

Monitoring time

[CnfVal] Supervision time

State

Supplies the present state of legionella prevention: Off | In progress | Successful | Not successful | Time slot expired

[MCalcVal] State

Primary return temperature sensor

Measures the primary return temperature.

[AI] Primary return temperature

Primary flow temperature sensor

Measures the primary flow temperature.

[AI] Primary flow temperature

Primary valve

Throttles the primary water volume to maintain the desired secondary flow temperature.

Valve (Primary) (Folder)

> [Controller] Temperature controller

Primary return temperature maximum limitation

Controls the maximum primary return temperature. The setpoint is fixed. It switches to a higher setpoint if the function for legionella prevention is active.

Limits the temperature controller for the water temperature to a minimum of e.g. 15%.

> [Controller] Limitation controller, maximum return temperature

Limitation active

Indicates that the output of the temperature controller for the hot water temperature is limited.

[BCalcVal] Limitation active

Positioning

[AO] Position

Functions and diagrams

Direct hot water handling

The hot water temperature is controlled directly using the primary valve. The controller is always operating when the plant is switched on. It is operated using a wider neutral zone (e.g. 4K) if there is no flow.

Flow detector function

An installed flow detector accelerates the reaction of direct hot water handling.

  • The flow detector reports flow: The minimum of the temperature controller output is increased as per a time matching the runtime of the actuator, for example from 0% to 25%. This precontrols the valve.
  • The flow detector no longer reports flow: The maximum of the temperature controller output is set for a short period to 0%. This forces the valve to close. In addition, the neutral zone of the temperature controller is increased, e.g. 4K.

Controller and its settings

Name

Description

Object type

Default value

Vlv(Prim)'TCtr

Temperature controller

Controls the secondary flow temperature.

Controller

N/A

The temperature controller acts as a PI controller (PID with derivative action time Tv=0) and compares the secondary flow temperature setpoint [PrSpTFlSec] against the secondary flow temperature [TFlSec] and calculates the valve position [Vlv(Prim)'Pos] on the output.

The following controller variables are preset:
- Controller gain: 2 [%/K]
- Integral action time Tn: 30 [s]

Vlv(Prim)'TRtCtrMax

Return temperature controller for maximum limitation (option).

Controls the maximum primary return temperature. The setpoint is generated in a floating manner based on outside temperature.

Controller

N/A

The temperature controller acts as a PI controller (PID with derivative action time Tv=0) and compares the floating setpoints based on the outside temperature against the primary return temperature [TRtPrim] and calculates a limitation to the valve position [Vlv(Prim)'Pos] on the output.

The following controller variables are preset:
- Controller gain: 2.5 [%/K]
- Integral action time Tn: 600 [s]

ScaPrt'TCtr

Scalding protection temperature controller

Limits the consumer hot water temperature.

Controller

N/A

The temperature controller acts as a PI controller (PID with derivative action time Tv=0) and compares the setpoint of e.g. 65 [°C] against the hot water temperature for the consumer [ScaPrt'TDhwCns] and calculates the valve position [ScaPrt'Vlv'Pos] on the output.

The following controller variables are preset:
- Controller gain: 2.5 [%/K]
- Integral action time Tn: 200 [s]

Legionella prevention

The function is used in hot water systems to prevent the growth of the legionella bacteria or as a thermal disinfectant to kill legionella.

Legionella are pathogenic bacteria. Legionella grow in warm water at temperatures of approximately 20 °C to 50 °C. Disinfection or killing legionella bacteria depends on temperature and time. They begin to die off at around 55 °C.

As a consequence, the hot water temperature must be increased daily or weekly for a specific time to disinfect. A scheduler exists in the scheduler to send a time pulse to start the function.

The function must be activated via time pulse. Hot water is heated to the legionella disinfection temperature during a defined period. The function succeeds and is canceled if the temperature remains above the disinfection temperature for the required duration. An alarm (LglPrev'Failed) is generated if conditions are not fulfilled during the required duration.

The state of the function is indicated on function block State:

1 - Off

2 - In progress

3 - Successful

4 - Not successful

5 - Time slot expired

Key

TTnkTop

Tank temperature, top

TTnkBtm

Tank temperature, bottom

Sp

Setpoint

Dmd

Storage tank charging control

SupyTI

Supervision time. The temperature must be above the setpoint during this period. Set on TiMon, e.g., 60 minutes.

ValCirPu

Request to the circulating pump

LglPrevAct

The function is active, and the conditions are not yet met.

Timer

Timeframe for maximum duration, e.g., 4 hours

LglSched/Timer

The time pulse from BSchedule triggers the function. During the timeframe timer, the temperature must be higher than the setpoint for an adjustable time. The function is then fulfilled.

BACnet objects

Name

Description

Object type

Default value

LglPrev'Sched

Scheduler program

BSchedule

N/A

LglPrev'Sta

State

MCalcVal

N/A

LglPrev'Failed

Legionella prevention failed

BCalcVal

N/A

LglPrev'Sp

Setpoint

ACnfVal

60 [°C]

LglPrev'TiMon

Monitoring time

CnfVal

60 min

During the period, the circulating pump is commanded at priority 4. A parameter determines whether the circulating pump is operating or is blocked.

The circulating pump is on continuously if the function for legionella prevention is active.

info

Legionella prevention is switched off in plant state 'Off' for domestic hot water handling. LglSched is, however, active. The impulse is saved if a start impulse for the function comes from LglSched and the plant state is 'Off'. The function is performed immediately once the plant state changes to 'On'.

Plant operating modes and control sequence

Plant operating modes:

  • Off (1)
  • On (2)

The operating modes are reported on [MCalcVal] object 'Present operating mode'.

At the same time, the reason for the present operating mode is reported to another [MCalcVal] object:

  • Exception (1)
  • Operating mode switch (2), resulting from an active (not equal to Auto) operating mode switch
  • Manual operating mode selection (3), resulting from an active (not equal to Auto) manual operating mode selection
  • Scheduler (4), resulting from an active scheduler

Normal operation

Sources for normal mode:

  • [MI] Operating mode switch
  • [MCnfVal] Manual operating mode selection
  • [MSchedule] Scheduler

In normal mode, components are simultaneously switched on and off as per the operating mode.

Exception mode

Sources for exception mode:

  • Fault in the primary pump
  • Fault in the secondary pump

In exception mode, all outputs are switched off directly at priority 5 and the present operating mode is set to 'Off'.

Start-up control and alarm handling

Start-up control (nested chart SttUpAlmHdl)

The following functionality is available for an automatic startup of the plant, e.g. after a loss of power and return of power:

  1. Fixed switch-on delay (can be set on input pin [DlySttUp])
  2. The plant remains off to ensure communications are reliable and cross-check references are triggered. 'Exception' is reported as the reason for the present operating mode.
  3. Automatic acknowledge (2x) of possible pending alarms during a fixed switch-on delay.
  4. Additional adjustable delay for staged plant ramp-up (can be set on input pin [DlyOn])

Alarm handling (nested chart SttUpAlmHdl)

The state of events on the plant is acquired by BACnet object 'Plant state'. The state is mapped on function block CMN_EVT.
[CMN_EVT] Common event

The following functions are available:

  1. Automatic acknowledge (2x) after startup
  2. Alarm acknowledgement with a value object
  3. Alarm indication:
    - For pending alarms On
    - For unprocessed alarms flashing
  4. Ability to connect the acknowledge button [BI]
  5. Ability to connect to an alarm indication [BO], e.g. an alarm lamp through an output block [BO]
  6. Ability to connect to other alarm handling functions on other plants, e.g. acknowledge button and alarm indication for multiple plants in the same control cabinet

Startup function and alarm handling for flat plants

I/O data points

Name

Description

Type

Signal/connection

State text

Engineering unit

OpModSwi

Operating mode switch

MI

N/A

Auto | Off | On

N/A

CirPu'Cmd

Circulating pump command

BO

NO contact

Off | On

N/A

FlDet

Flow detector

BI

NO contact

No flow | Flow

N/A

ScaPrt'TDhwCns

Scalding prevention consumer hot water temperature

Alarm function: Basic (Notification class 8)

Limit high 75 [°C]; limit low 0 [°C]

Time deviation: 30 [s]

AI

LG-Ni1000

N/A

0...100 [°C]

ScaPrt'Vlv

Scalding protection valve position

AO

0...10V

N/A

0...100 [%]

TDhw

Domestic hot water temperature.

Alarm function: Basic (Notification class 8)

Limit high 75 [°C]; limit low 0 [°C]

Time deviation: 30 [s]

AI

LG-Ni1000

N/A

0...100 [°C]

TFlPrim

Primary flow temperature

AI

LG-Ni1000

N/A

0...100 [°C]

TRtPrim

Primary return temperature

AI

LG-Ni1000

N/A

0...100 [°C]

Vlv(Prim)'Pos

Valve (primary) position

AO

0...10V

N/A

0...100 [%]