[Mntn21] Maintenance, operating hours-dependent

Program block, name / node subtype: [Mntn21] Maintenance, operating hours-dependent

Library hierarchy: Universal functions

Family: Mntn

Project tree

Diagram

Configurator

info

Program blocks are stored in the library without I/Os. Use the auto-create and auto-connect functions to create I/Os and/or to connect them to the interface blocks, e.g., R_A, CMD_B. Alternatively, take the I/Os from the folder containing the predefined I/Os in the library and/or from the plant and connect them to the interface blocks.

Function

Counts operating hours and generates maintenance indication when reaching a limit for maintenance.

The operating hours are calculated with function block INTEGRAL. It is set up so that its output shows the number of operating hours. The resolution is 1 hour.

The function can be reset with a software switch.

info

This program block is almost identical to AFil22.

Mandatory elements

Name

Description

Type

Alarm / Notification class

Trend / Type

RstOph

Reset operating hours

BCnfVal: Binary configuration value

No

No

MntnLm

Maintenance limit

ICnfVal: Integer configuration value

No

No

MntnInd

Maintenance indication

BCalcVal: Binary calculated value

Yes, 8

No

OpSta

Operating state

BCalcVal: Binary calculated value

No

No

Oph

Operating hours

ICalcVal: Integer calculated value

No

No