[Mntn21] Maintenance, operating hours-dependent
Program block, name / node subtype: [Mntn21] Maintenance, operating hours-dependent
Library hierarchy: Universal functions
Family: Mntn
Project tree | Diagram |
|---|---|
|
|
|
Configurator


Program blocks are stored in the library without I/Os. Use the auto-create and auto-connect functions to create I/Os and/or to connect them to the interface blocks, e.g., R_A, CMD_B. Alternatively, take the I/Os from the folder containing the predefined I/Os in the library and/or from the plant and connect them to the interface blocks.
Counts operating hours and generates maintenance indication when reaching a limit for maintenance.
The operating hours are calculated with function block INTEGRAL. It is set up so that its output shows the number of operating hours. The resolution is 1 hour.
The function can be reset with a software switch.

This program block is almost identical to AFil22.
Name | Description | Type | Alarm / Notification class | Trend / Type | |
|---|---|---|---|---|---|
RstOph | Reset operating hours | BCnfVal: Binary configuration value | No | No | |
MntnLm | Maintenance limit | ICnfVal: Integer configuration value | No | No | |
MntnInd | Maintenance indication | BCalcVal: Binary calculated value | Yes, 8 | No | |
OpSta | Operating state | BCalcVal: Binary calculated value | No | No | |
Oph | Operating hours | ICalcVal: Integer calculated value | No | No | |