[AFil22] Air filter, with filter operating message
Program block, name / node subtype: [AFil22] Air filter, with filter operating message
Library hierarchy: Ventilation and air conditioning equipment
Family: Fil
Project tree | Diagram |
|---|---|
|
|
|
Configurator


Program blocks are stored in the library without I/Os. Use the auto-create and auto-connect functions to create I/Os and/or to connect them to the interface blocks, e.g., R_A, CMD_B. Alternatively, take the I/Os from the folder containing the predefined I/Os in the library and/or from the plant and connect them to the interface blocks.
Monitors an air filter and generates a maintenance indication when the filter has reached its operating hour limit.

This type of air filter monitoring can be used for special types of air filters, e.g., activated carbon filters, where a differential pressure switch or sensor cannot be used.

This program block is almost identical to Mntn21.
Name | Description | Type | Alarm / Notification class | Trend / Type |
|---|---|---|---|---|
RstOph | Reset operating hours | BCnfVal: Binary configuration value | No | No |
MntnLm | Maintenance limit | ICnfVal: Integer configuration value | No | No |
MntnInd | Maintenance indication | BCalcVal: Binary calculated value | Yes, 8 | No |
OpSta | Operating state | BCalcVal: Binary calculated value | No | No |
Oph | Operating hours | ICalcVal: Integer calculated value | No | No |