[AFil22] Air filter, with filter operating message

Program block, name / node subtype: [AFil22] Air filter, with filter operating message

Library hierarchy: Ventilation and air conditioning equipment

Family: Fil

Project tree

Diagram

Configurator

info

Program blocks are stored in the library without I/Os. Use the auto-create and auto-connect functions to create I/Os and/or to connect them to the interface blocks, e.g., R_A, CMD_B. Alternatively, take the I/Os from the folder containing the predefined I/Os in the library and/or from the plant and connect them to the interface blocks.

Function

Monitors an air filter and generates a maintenance indication when the filter has reached its operating hour limit.

info

This type of air filter monitoring can be used for special types of air filters, e.g., activated carbon filters, where a differential pressure switch or sensor cannot be used.

info

This program block is almost identical to Mntn21.

Mandatory elements

Name

Description

Type

Alarm / Notification class

Trend / Type

RstOph

Reset operating hours

BCnfVal: Binary configuration value

No

No

MntnLm

Maintenance limit

ICnfVal: Integer configuration value

No

No

MntnInd

Maintenance indication

BCalcVal: Binary calculated value

Yes, 8

No

OpSta

Operating state

BCalcVal: Binary calculated value

No

No

Oph

Operating hours

ICalcVal: Integer calculated value

No

No