[AFil23] Air filter, with differential pressure sensor and maintenance indication

Program block, name / node subtype: [AFil23] Air filter, with differential pressure sensor and maintenance indication

Library hierarchy: Ventilation and air conditioning equipment

Family: Fil

Project tree

Diagram

Configurator

info

Program blocks are stored in the library without I/Os. Use the auto-create and auto-connect functions to create I/Os and/or to connect them to the interface blocks, e.g., R_A, CMD_B. Alternatively, take the I/Os from the folder containing the predefined I/Os in the library and/or from the plant and connect them to the interface blocks.

Function

Monitors an air filter with a differential pressure sensor.

The characteristic of the filter element (differential pressure across the clean filter element for a given air volume flow) is set in the program (function block of type CHAR). This characteristic should be available in the filter manufacturer's documentation. Normally, the monoblock contains several filter elements. Their number must be set in the program. The measured air flow in the supply or extract air is divided by the number of filter elements and the resulting air flow per filter element is used for the function block CHAR.

The differential pressure across the filter is compared to the differential pressure for clean filter for the current air flow (from the function block CHAR). A maintenance indication is generated if the differential pressure reaches one of the limits calculated in the following way:

  • Differential pressure for clean filter for the current air flow plus an offset (e.g., + 100 Pa)
  • Differential pressure for clean filter for the current air flow multiplied by a factor (e.g., 3)
Mandatory elements

Name

Description

Type

Alarm / Notification class

Trend / Type

DiffP

Differential pressure

AI: Analog input

No

Yes, 2

MntnLmFac

Maintenance limit factor

ACnfVal: Analog configuration value

No

No

MntnLmOfs

Maintenance limit offset

ACnfVal: Analog configuration value

No

No

PrMntnLm

Present maintenance limit

ACalcVal: Analog calculated value

No

No

MntnInd

Maintenance indication

BCalcVal: Binary calculated value

Yes, 8

No

info

Set the number of filter elements in the Programming editor accordingly.