[Dmp24] Damper, modulating control and position feedback
Program block, name / node subtype: [Dmp24] Damper, modulating control and position feedback
Library hierarchy: Ventilation and air conditioning equipment
Family: Dmp
Project tree | Diagram |
|---|---|
|
|
|
Configurator


Program blocks are stored in the library without I/Os. Use the auto-create and auto-connect functions to create I/Os and/or to connect them to the interface blocks, e.g., R_A, CMD_B. Alternatively, take the I/Os from the folder containing the predefined I/Os in the library and/or from the plant and connect them to the interface blocks.
Controls the position of a damper (0-100 %).
This program block has the following optional functions:
Option: Fault (1xBI)
Reads a fault contact and generates an alarm.

This option is mainly used for dampers with actuators that are integrated over bus, e.g., Modbus.
Option: Position feedback (1xAI)
Reads the position of the damper.

"Position feedback" only reads the position and does not generate an alarm.
Name | Description | Type | Alarm / Notification class | Trend / Type |
|---|---|---|---|---|
Pos | Position | AO: Analog output | No | Yes, 2 |
Name | Description | Type | Alarm / Notification class | Trend / Type |
|---|---|---|---|---|
FbPos | Position feedback | AI: Analog input | No | Yes, 2 |
Flt | Fault | BI: Binary input | Yes, 4 | No |