[Dmp24] Damper, modulating control and position feedback

Program block, name / node subtype: [Dmp24] Damper, modulating control and position feedback

Library hierarchy: Ventilation and air conditioning equipment

Family: Dmp

Project tree

Diagram

Configurator

info

Program blocks are stored in the library without I/Os. Use the auto-create and auto-connect functions to create I/Os and/or to connect them to the interface blocks, e.g., R_A, CMD_B. Alternatively, take the I/Os from the folder containing the predefined I/Os in the library and/or from the plant and connect them to the interface blocks.

Function

Controls the position of a damper (0-100 %).

This program block has the following optional functions:

Option: Fault (1xBI)

Reads a fault contact and generates an alarm.

info

This option is mainly used for dampers with actuators that are integrated over bus, e.g., Modbus.

Option: Position feedback (1xAI)

Reads the position of the damper.

info

"Position feedback" only reads the position and does not generate an alarm.

Mandatory elements

Name

Description

Type

Alarm / Notification class

Trend / Type

Pos

Position

AO: Analog output

No

Yes, 2

Optional elements

Name

Description

Type

Alarm / Notification class

Trend / Type

FbPos

Position feedback

AI: Analog input

No

Yes, 2

Flt

Fault

BI: Binary input

Yes, 4

No