[HuCasCtr21] Humidity cascade controller, relative room/extract humidity and absolute supply humidity

Program block, name / node subtype: [HuCasCtr21] Humidity cascade controller, relative room/extract humidity and absolute supply humidity

Library hierarchy: Ventilation and air conditioning functions

Family: HuCtr

Project tree

Diagram

Configurator

info

Program blocks are stored in the library without I/Os. Use the auto-create and auto-connect functions to create I/Os and/or to connect them to the interface blocks, e.g., R_A, CMD_B. Alternatively, take the I/Os from the folder containing the predefined I/Os in the library and/or from the plant and connect them to the interface blocks.

Function

Performs cascade control and calculates the supply air humidity setpoints (in g/kg) with the aid of a function block of type CAS_CTR and maps its inputs and output to BACnet with multiple value objects.

The calculated supply temperature setpoints are limited to a minimum and maximum.

Mandatory elements

Name

Description

Type

Alarm / Notification class

Trend / Type

CasCtr

Cascade controller

CAS_CTR: Cascade controller

N/A

N/A

Gain

Gain

ACnfVal: Analog configuration value

No

No

Tn

Integral action time Tn

ICnfVal: Integer configuration value

No

No

SpHuSuMax

Maximum setpoint for supply air humidity

ACnfVal: Analog configuration value

No

No

SpHuSuMin

Minimum setpoint for supply air humidity

ACnfVal: Analog configuration value

No

No

PrSpHiHuSu

Present setpoint high for supply air humidity

ACalcVal: Analog calculated value

No

No

PrSpLoHuSu

Present setpoint low for supply air humidity

ACalcVal: Analog calculated value

No

No

PrSpHuSu

Present setpoint supply air humidity

ACalcVal: Analog calculated value

No

No

PrSpHiHu

Present setpoint high for room humidity

ACalcVal: Analog calculated value

No

No

PrSpLoHu

Present setpoint low for room humidity

ACalcVal: Analog calculated value

No

No