[HuSuCtr21] Supply humidity controller, relative supply humidity
Program block, name / node subtype: [HuSuCtr21] Supply humidity controller, relative supply humidity
Library hierarchy: Ventilation and air conditioning functions
Family: HuCtr
Project tree | Diagram |
|---|---|
|
|
|
Configurator


Program blocks are stored in the library without I/Os. Use the auto-create and auto-connect functions to create I/Os and/or to connect them to the interface blocks, e.g., R_A, CMD_B. Alternatively, take the I/Os from the folder containing the predefined I/Os in the library and/or from the plant and connect them to the interface blocks.
Provides supply air humidity setpoints.
They are limited to a minimum and maximum.

The input pins [Hu] and [HuSu] are there only to ensure the compatibility to HuCasCtr21 and are not interconnected internally.
Name | Description | Type | Alarm / Notification class | Trend / Type |
|---|---|---|---|---|
|
SpHuSuMax | Maximum setpoint for supply air humidity | ACnfVal: Analog configuration value | No | No |
SpHuSuMin | Minimum setpoint for supply air humidity | ACnfVal: Analog configuration value | No | No |
PrSpHiHuSu | Present setpoint high for supply air humidity | ACalcVal: Analog calculated value | No | No |
PrSpLoHuSu | Present setpoint low for supply air humidity | ACalcVal: Analog calculated value | No | No |
PrSpHuSu | Present setpoint supply air humidity | ACalcVal: Analog calculated value | No | No |
PrSpHiHu | Present setpoint high for room humidity | ACalcVal: Analog calculated value | No | No |
PrSpLoHu | Present setpoint low for room humidity | ACalcVal: Analog calculated value | No | No |

This module is called controller, however it doesn't contain a controller. This module is an alternative to a module with a cascade controller. It connects the plant's setpoints for humidification and dehumidification to the supply air setpoints and limits them.