[NgtC21] Night cooling, based on the operating mode in the rooms and temperature values

Program block, name / node subtype: [NgtC21] Night cooling, based on the operating mode in the rooms and temperature values

Library hierarchy: Ventilation and air conditioning functions

Family: NgtC

Project tree

Diagram

Configurator

info

Program blocks are stored in the library without I/Os. Use the auto-create and auto-connect functions to create I/Os and/or to connect them to the interface blocks, e.g., R_A, CMD_B. Alternatively, take the I/Os from the folder containing the predefined I/Os in the library and/or from the plant and connect them to the interface blocks.

Function

Enables a "Night cooling" operation mode if the following conditions are met (NgtC21):

  1. The plant is off.
  2. The "Night cooling" is enabled by its own scheduler.
  3. The outside temperature is not too low.
  4. The difference between the room temperature and the outside temperature is high enough.
  5. The room temperature is not below the heating setpoint.

Stops the plant and the "Night cooling" operation mode if any of the above conditions are not met.

During "Night cooling":

Some aggregates are on (dampers are opened, fans are running, coils are off, control components, except for the logic for night cooling are off).

Mandatory elements

Name

Description

Type

Alarm / Notification class

Trend / Type

Sched

Scheduler

BSchedule: Binary scheduler

N/A

N/A

TOaLoLm

Outside air temperature low limit

ACnfVal: Analog configuration value

No

No

SwiOnDT

Switch-on via temperature difference

ACnfVal: Analog configuration value

No

No

info

This function needs values for outside temperature and setpoint heating.