[TCasCtr21] Temperature cascade controller, supply air setpoint high/low and for energy recovery

Program block, name / node subtype: [TCasCtr21] Temperature cascade controller, supply air setpoint high/low and for energy recovery

Library hierarchy: Ventilation and air conditioning functions

Family: TCtr

Project tree

Diagram

Configurator

info

Program blocks are stored in the library without I/Os. Use the auto-create and auto-connect functions to create I/Os and/or to connect them to the interface blocks, e.g., R_A, CMD_B. Alternatively, take the I/Os from the folder containing the predefined I/Os in the library and/or from the plant and connect them to the interface blocks.

Function

Performs cascade control.

Calculates the supply temperature setpoints with a function block of type CAS_CTR.

Maps its inputs and outputs to BACnet with multiple value objects.

The calculated supply temperature setpoints are limited to a minimum and a maximum.

info

You can select the calculation method of the temperature setpoint for the energy recovery. It is either equal to the heating or cooling supply temperature setpoint and depends on the present direction of the control action (CAS_CTR.SelSpErc=0, preset), or equal to their average (CAS_CTR.SelSpErc=1).

info

An analog calculated value can be read from the device chart of a room unit.

Mandatory elements

Name

Description

Type

Alarm / Notification class

Trend / Type

CasCtr

Cascade controller

CAS_CTR: Cascade controller

N/A

N/A

Gain

Gain

ACnfVal: Analog configuration value

No

No

Tn

Integral action time Tn

ICnfVal: Integer configuration value

No

No

SpTSuMax

Maximum supply air temperature setpoint

ACnfVal: Analog configuration value

No

No

SpTSuMin

Minimum supply air temperature setpoint

ACnfVal: Analog configuration value

No

No

PrSpHiT

Present setpoint high for room temperature

ACalcVal: Analog calculated value

No

No

PrSpLoT

Present setpoint low for room temperature

ACalcVal: Analog calculated value

No

No

PrSpHiTSu

Present setpoint high for supply air temperature

ACalcVal: Analog calculated value

No

No

PrSpLoTSu

Present setpoint low for supply air temperature

ACalcVal: Analog calculated value

No

No

PrSpErcTSu

Present setpoint energy recovery for supply air temperature

ACalcVal: Analog calculated value

No

No

PrSpTSu

Present setpoint supply temperature

ACalcVal: Analog calculated value

No

No