[TSuCtr21] Supply air temperature controller

Program block, name / node subtype: [TSuCtr21] Supply air temperature controller

Library hierarchy: Ventilation and air conditioning functions

Family: TCtr

Project tree

Diagram

Configurator

info

Program blocks are stored in the library without I/Os. Use the auto-create and auto-connect functions to create I/Os and/or to connect them to the interface blocks, e.g., R_A, CMD_B. Alternatively, take the I/Os from the folder containing the predefined I/Os in the library and/or from the plant and connect them to the interface blocks.

Function

Provides supply temperature setpoints.

The setpoints are limited to a minimum and a maximum.

info

You can select the calculation method of the temperature setpoint for the energy recovery. It is either equal to the heating or cooling supply temperature setpoint and depends on the present direction of the control action (preset), or equal to their average.

info

The input pins [T] and [TSu] are only present to ensure the compatibility to TCasCtr21 and are not interconnected internally.

Mandatory elements

Name

Description

Type

Alarm / Notification class

Trend / Type

SpTSuMax

Maximum supply air temperature setpoint

ACnfVal: Analog configuration value

No

No

SpTSuMin

Minimum supply air temperature setpoint

ACnfVal: Analog configuration value

No

No

PrSpErcTSu

Present setpoint energy recovery for supply air temperature

ACalcVal: Analog calculated value

No

No

PrSpHiT

Present setpoint high for room temperature

ACalcVal: Analog calculated value

No

No

PrSpLoT

Present setpoint low for room temperature

ACalcVal: Analog calculated value

No

No

PrSpHiTSu

Present setpoint high for supply air temperature

ACalcVal: Analog calculated value

No

No

PrSpLoTSu

Present setpoint low for supply air temperature

ACalcVal: Analog calculated value

No

No

PrSpTSu

Present setpoint supply temperature

ACalcVal: Analog calculated value

No

No

info

This module is called controller, however it doesn't contain a controller. This module is an alternative to a module with a cascade controller. It connects the plant's setpoints for heating and cooling to the supply air setpoints and limits them.