[Fdp29] Fire damper, open/close function & MI for feedback

Program block, name / node subtype: [Fdp29] Fire damper, open/close function & MI for feedback

Library hierarchy: Ventilation and air conditioning equipment

Family: Fdp

Project tree

Diagram

Configurator

info

Program blocks are stored in the library without I/Os. Use the auto-create and auto-connect functions to create I/Os and/or to connect them to the interface blocks, e.g., R_A, CMD_B. Alternatively, take the I/Os from the folder containing the predefined I/Os in the library and/or from the plant and connect them to the interface blocks.

Function

Controls a fire damper with open/close function and optional feedback signals and fault alarm.

info

This program block is mainly used as an alternative to Fdp21.

info

The opening and closing time can be parameterized in the program.

This program block has the following optional functions:

Option: Fault (1xBI)

Reads a fault contact and generates an alarm.

info

This option is mainly used for dampers with actuators that are integrated over bus, e.g., Modbus.

Option: Feedback (1xMI=2xBI)

Reads the end switches of the actuator for the opened and closed position of the damper.

Mandatory elements

Name

Description

Type

Alarm / Notification class

Trend / Type

Cmd

Command

BO: Binary output

No

Yes, 4

Optional elements

Name

Description

Type

Alarm / Notification class

Trend / Type

Fb

Feedback

MI: Multistate input

No

No

Further elements that belong to this element:

PosMon (Opnd) | Position monitoring (Opened) | BCalcVal: Binary calculated value | Alarm: Yes | Notification class 4

PosMon (Clsd) | Position monitoring (Closed) | BCalcVal: Binary calculated value | Alarm: Yes | Notification class 4

Flt

Fault

BI: Binary input

Yes, 4

No