Balancing air/water (with Pack & Go)
Working with a Pack & Go file is optional. In some cases the balancer creates a project and performs a discovery.
Balancing air/water (with discovery)
Prepare and handover working package for balancer
1 | Open Building > Building structure. | |
2 | Create a Pack & Go file. | |
3 | Handover data to balancer (subcontractor): -- Pack & Go file (*.txt, *.ABTGo) -- User name and password -- ABT Site installation package |
|
Balance an ABT project
- | ABT Site is installed (Setup.exe). Pack & Go files (*.txt, *.ABTGo) are local on the laptop. |
|
1 | Double click the Pack & Go file (*.ABTGo). ABT Site starts and loads the Pack & Go data. Open an ABT project. |
|
2 | Set up the connection. | |
3 | Connect the laptop to the automation station. | |
4 | Open Startup > Global functions. | |
5 | Issue Global commands: --Select parameters --Select engineered or discovered automation stations. | |
6 | Balance automation stations: --Select an automation station and Go to web interface --Follow procedure for air or water balancing |
|
7 | Release Global commands. | |
8 | Repeat steps 4 through 6 for all automation stations. |
|
9 | Update online report data. | |
10 | Create a report. | Reports |
11 | Open Startup > Export. | |
12 | Create Pack & Return file. | |
13 | Handover following data to project owner (optional) -- Pack & Return file (*.ABTReturn) |
|
Possible next step: complete an ABT project.