Commissioning an ABT project
Commission the project data
1 | In Building > Building structure, adjust object naming, adjust rooms / room segments | |
2 | In Building > Central function, adjust grouping (central functions) | |
3 | In Startup > Configure and download, download the configuration (template). |
Update project data, types, templates, firmware
1 | Open Startup > Configure and download. | |
2 | If necessary, update the firmware. | |
3 | If necessary, update the user profile. |
Commission the ABT project
1 | Open Startup > Global functions. | |
2 | Launch the web interface of the automation station (go to web interface). | |
3 | The web interface opens in ABT Site > Online > AS... |
|
4 | Test application functions: -- Command switches to test switching conditions, type of action, mode of functioning, scenes. -- Command switches or sensors to test assignment of devices to groups (central functions). |
|
5 | Test alarming and scheduling: -- Command values to trigger alarms. -- Set values to trigger schedules. | Monitoring and operating |
6 | Commission the configured application in the room (online): -- Test room functions -- Change a single configuration parameter. -- Configure scenes, etc. -- Mass change of parameters -- Change multiple parameters by work packages. | Monitoring and operating |
7 | Create data point commissioning reports. | |
8 | Open Startup > Configure and download. | |
9 | Update the project data base with the current device configuration of automation stations: -- Upload device configuration (i.e., PXC). | Uploading a device configuration |
Possible next step: completing the main project.
Completing an ABT project