Application & device overview

The Application & device overview task allows you to manage application templates, and start the Configuration component in order to create and modify application templates.

1

Task selector

2

Work area: Application templates table

3

Details pane

4

Toolbar

5

Context menu

 

 

 

① Task selector

Column

Description

Building Structure

Building structure

Central functions

Central functions

Device list

Device list

Application & device overview

Current task

Certificates management

Certificates management

Network check

Network check

BACnet/SC

BACnet/SC

② Work area: Application templates table

Column

Description

Status

Status of the room/automation station.
Activity states

Name

Name of the application template or automation station.

Description

Description of the application template or automation station.

Location

Location of the application template or automation station.

Version

Displays the version number of the application template. If a new version of the application type is found, Update displays in the Version column.
Updating application templates and graphics libraries

Note
The value in the Version column is managed by the user.

③ Details pane

The contents of the Details pane vary depending on the selected element.
Building element details
Details pane of the device version ≤ 1.5
Room and segment details
Application template details

 

④ Toolbar

Command

Description

Split view

Splits the work area vertically to get two views of the same building, allowing you to move elements from one view to another.

Remove split

Resets the view to one work area.

Go to configuration

Opens Configuration > Application configuration where you can reconfigure the selected application template.

Note
In case of changing an already downloaded template: All configured and commissioned data in the online system are overwritten. To prevent data loss, read back the online system data to ABT Site before making offline changes in the template.

Go to engineering

Opens the Engineering component. Only available for operating and monitoring devices, or bus interface modules.

Note
Default action: Double-click a device to open the Engineering component.
Engineering

Change device

If an existing device type PXC4 or PXC5 is no longer sufficient, it can be changed to a larger device type.

Changing the device type (network or size)

Note

Changing a device type with onboard I/Os requires a new assignment if a device type with I/O modules is used.

Delete

Deletes the selected element and its children.

Check for updates

Compares the used application templates against the installed templates from the library. This check is performed for each application template, based on the application type name, version, and the system of units.
Updating application templates and graphics libraries

⑤ Context menu

Command

Description

Edit

Highlights the selected column value for renaming.

Delete

Deletes the selected element and its children.

Go to building structure

Opens the Building structure component. Add and delete building elements and devices. Modify device properties.
Building structure

Go to engineering

Opens the Engineering component. Only available for operating and monitoring devices, or bus interface modules.

Note
Default action: Double-click a device to open the Engineering component.
Engineering

Go to programming

Opens the Programming editor.

Go to startup

Opens the Startup component.

Go to configuration

Opens Configuration > Application configuration where you can reconfigure the selected application template.

Note
In case of changing an already downloaded template: All configured and commissioned data in the online system are overwritten. To prevent data loss, read back the online system data to ABT Site before making offline changes in the template.

Start/Stop simulation

Starts/stops simulation of the selected device to test its logical workflow.

Performing program simulation

Use as base for new application template

Generates a new application template based on the selected automation station.
Splitting application templates

Export application template

Opens a dialog box where you can select a folder to save the application template, so you can share it with other projects and users.
When exporting a template, a *.s1ct file is created.
Exporting application templates

Create program

Creates a new project in ABT Pro with the name of the selected application template. Enables the user to reengineer the application template in ABT Pro.

Duplicate application template and go to Programming

Opens the dialog Duplicate application template. Enter the properties of the new application template and click OK to start room programming.

Create Pack & Go

Opens the Create Pack & Go dialog box to create a Pack & Go file.
Creating a Pack & Go file

Apply notification classes

Applies the notification class template according the project settings.

Device defaults
Checking the notification classes template in the project

Set commissioned

Set the status for the selected automation stations to Commissioning done.

Reports

Opens the Selectreport dialog box to select one or more reports to be created in the selected context.
Types of reports

Application help

Opens the corresponding help file.

Properties

Opens the Details pane.
Details pane